8.5.5

Dimension drawing

Figure 8-24
Dimension drawing of Safe Brake Relay, all data in mm and (inches)
8.5.6

Mounting

The Safe Brake Relay is installed at the rear of the cabinet next to the Power Module.
8.5.7

Technical data

Table 8- 26
Technical data
6SL3252-0BB01-0AA0
Power supply
Current requirement, max.
Motor brake
at 24 V DC
Conductor cross section, max.
Dimensions (W x H x D)
Weight
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
Supplementary system components and encoder system integration
Unit
V
20.4 ... 28.8
DC
Recommended nominal value of the power supply 26 V DC
(to equalize and compensate for the voltage drop along the feeder
cable to the 24 V DC solenoid of the motor brake)
A
2
A
0.05 + current requirement of the motor brake
mm
2.5
2
mm
69 x 63 x 33
kg
approx. 0.17
8.5 Option module Safe Brake Relay
211