X524 Electronics Power Supply - Siemens SINAMICS S110 Manual

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

NOTICE
Damage to motor due to incorrectly connected KTY temperature sensor
If a KTY temperature sensor is connected with incorrect polarity, it is not possible to detect
when the motor overheats. Overheating can cause damage to the motor.
• Connect a KTY temperature sensor with the correct polarity.
Danger to life due to electric shock in the event of voltage flashovers on the temperature
sensor cable
Voltage flashovers in the signal electronics can occur in motors without safe electrical
separation of the temperature sensors.
• Only use temperature sensors that fully comply with the specifications of the safety
• If safe electrical separation cannot be guaranteed (for linear motors or third-party
8.3.3.4

X524 Electronics power supply

Table 8- 11
X524: Electronics power supply
Terminal
+
+
M
M
Type: Screw-type terminal (Page 263)
Max. cross section that can be connected: 2.5 mm²
The maximum cable length that can be connected is 30 m.
Note
The two "+" or "M" terminals are jumpered in the connector. This ensures that the supply
voltage is looped through.
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
Supplementary system components and encoder system integration
WARNING
isolation.
motors, for example), use a Sensor Module External (SME120 or SME125) or Terminal
Module TM120.
Function
Electronics power supply
Electronics power supply
Electronics ground
Electronics ground
8.3 Sensor Module Cabinet-Mounted SMC20
Technical data
Voltage: 24 V (20.4 ... 28.8 V)
Current consumption: Max. 0.35 A
Maximum current via jumper in connector: 20 A (15 A
according to UL/CSA)
185