X100 Drive-Cliq Interface; X124 Electronics Power Supply - Siemens SINAMICS S110 Manual

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

CU305 Control Units
7.3 Interface description
7.3.5.4

X100 DRIVE-CLiQ interface

Table 7- 15
Connector type DRIVE-CLiQ socket
The blanking cover for the DRIVE-CLiQ port is included in the scope of delivery.
Blanking covers (50 x) Article No:: 6SL3066-4CA00-0AA0
Note
The maximum DRIVE-CLiQ cable length is 100 m.
7.3.5.5

X124 Electronics power supply

Table 7- 16
Type: Screw-type terminal (Page 263)
Max. cross section that can be connected: 2.5 mm
The maximum cable length that can be connected is 30 m.
Note
The two "+" or "M" terminals are jumpered in the connector. This ensures that the supply
voltage is looped through.
146
X100 DRIVE-CLiQ interface
Pin
Signal name
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
B
M (0 V)
X124 electronics power supply
Terminal
Function
+
Electronics power supply
+
Electronics power supply
M
Electronics ground
M
Electronics ground
Technical data
Transmit data +
Transmit data -
Receive data +
Receive data -
Power supply
Electronics ground
Technical data
Voltage: 24 V DC (20.4 to 28.8 V)
Current consumption: max. 0.8 A (incl. 0.35
A for HTL encoders, without DRIVE-CLiQ
and digital outputs)
Max. current via jumper in connector: 20 A
(15 A according to UL/CSA)
2
Manual, 07/2015, 6SL3097-4AC10-0BP5
SINAMICS S110

Advertisement

Table of Contents
loading