7.3.4.2
X126 CAN interface
Table 7- 7
Type: 9-way Sub-D socket
NOTICE
Damage to the CAN interface if a PROFIBUS connector is connected
If a PROFIBUS connector is connected to the CAN interface, the interface may be
damaged.
• Do not connect a PROFIBUS connector to the CAN interface.
7.3.4.3
S100 DIP switch
Table 7- 8
Switch
2
1
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
X126 CAN interface
Pin
Signal name
1
Reserved, do not use
2
CAN_L
3
CAN_GND
4
Reserved, do not use
5
CAN_SHL
6
CAN_GND
7
CAN_H
8
Reserved, do not use
9
Reserved, do not use
DIP switch
Function
Switch setting
Bus terminating
Off
resistor
On
120 Ohm
Operation
Off
with/without ground
On
CU305 Control Units
7.3 Interface description
Technical data
CAN signal
CAN ground
Optional shield
CAN ground
CAN signal
Default
Inactive
Off
Active
Ungrounded opera-
Off
tion
Grounded opera-
tion
139