System Data - Siemens SINAMICS S110 Manual

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

2.4

System data

Table 2- 1
Electrical data
Line voltage
Line frequency
Output voltage
Rated pulse frequency
For Power Modules with line voltages 1/3 AC 200 ... 240 V or 3 AC 380 ... 480 V and a type rating of I
kHz
The pulse frequency can be increased in steps of 2 kHz; the maximum value is listed in the Technical Data of the relevant
Power Module. On overload, a reduction to 2 kHz is permitted.
If the rated pulse frequency is exceeded, you must consider the associated characteristics for the current derating. You will
find more information in Chapter Derating (Page 31).
Electronic power supply
Short-circuit current rating SCCR
in accordance with UL508C (up to 600 V)
EMC Directive
acc. to EN 61800-3
Overvoltage category
Pollution degree
If a motor holding brake is used, restricted voltage tolerances (±10 %) may have to be taken into account.
1)
Table 2- 2
Environmental conditions
Degree of protection
Protection class
Power circuits
Electronic circuits
Type of cooling
Permissible cooling medium temperature (air)
and installation altitude during operation
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
FSA ... FSC:
1/3 AC: 200 ... 240 V ±10 %
3-phase AC: 380 ... 480 V ±10 %
FSD ... FSE
3 AC: 380 ... 480 V -20/+10 %
47 ... 63 Hz
1-phase AC: 0 V to 0.74 · line voltage
3-phase AC: 0 V to 0.95 · line voltage
24 V DC -15/+20%
, protective/safe extra low voltage (PELV/SELV)
1)
1.1 ... 447 kW: 65 kA
UL approval applies only in conjunction with the fuses prescribed by
Siemens and not with other types or circuit breakers alone.
Category C3 (option)
Category C2 (option)
Category C1 (option)
for systems implemented in conformance with the documentation
III
2
IPXXB according to EN 60529, open type according to UL 508
I (with PE conductor connection)
III (protective/safe extra low voltage PELV/SELV)
Internal air cooling,
power units with forced air cooling using an integrated fan
External air cooling
0°C ... +40°C and up to 1000 m installation altitude: Without derat-
ing
> +40 ... +60°C: See characteristic for current derating
Installation altitude > 1000 m ... 4000 m: See characteristic for cur-
rent derating or reduction of the ambient temperature by 3.5 K per
500 m
System overview
2.4 System data
< 110 kW: 4
n
29

Advertisement

Table of Contents
loading

Table of Contents