X524 Electronics Power Supply; Connection Examples - Siemens SINAMICS S110 Manual

Hide thumbs Also See for SINAMICS S110:
Table of Contents

Advertisement

8.4.3.5

X524 Electronics power supply

Table 8- 17
X524: Electronics power supply
Terminal
+
+
M
M
Type: Screw-type terminal (Page 263)
Max. cross section that can be connected: 2.5 mm²
The maximum cable length that can be connected is 30 m.
Note
The two "+" or "M" terminals are jumpered in the connector. This ensures that the supply
voltage is looped through.
8.4.4

Connection examples

Connection example 1: HTL encoder, bipolar, with reference signal
Figure 8-12
Signal cables must be twisted in pairs to improve immunity to induced noise.
SINAMICS S110
Manual, 07/2015, 6SL3097-4AC10-0BP5
Supplementary system components and encoder system integration
Function
Electronics power supply
Electronics power supply
Electronics ground
Electronics ground
Connection example 1: HTL encoder, bipolar, with reference signal
8.4 Sensor Module Cabinet-Mounted SMC30
Technical data
Voltage: 24 V (20.4 ... 28.8 V)
Current consumption: Max. 0.35 A
Maximum current via jumper in connector: 20 A (15 A
according to UL/CSA)
197

Advertisement

Table of Contents
loading

Table of Contents