The devices are "open equipment" according to the standard IEC 61010-2-201 or UL
61010-2-201 / CSA C22.2 No. 61010-2-201. To fulfill requirements for safe operation with
regard to mechanical stability, flame retardation, stability, and protection against contact, the
following alternative types of installation are specified:
• Installation in a suitable cabinet.
• Installation in a suitable enclosure.
• Installation in a suitably equipped, enclosed control room.
If the temperature at the cable or housing socket or at the branching points of the cables
exceeds 60 °C, special precautions must be taken. If the equipment is operated at ambient
temperatures in excess of 40 °C, only use cables with permitted operating temperature of at
least 80 ℃.
Further notes
NOTICE
Warming and premature aging of the network component due to direct sunlight
Direct sunlight can heat up the device and can lead to premature aging of the network
component and its cabling.
Provide suitable shade to protect the network component against direct sunlight.
6.2

Mounting types

The following mounting types are provided for the SCALANCE XCM-100:
• DIN rail
• S7-300 mounting rail
• S7-1500 mounting rail
• Wall mounting
SCALANCE XCM-100 Media Converter
Operating Instructions, 07/2022, C79000-G8976-C659-01
WARNING
WARNING
Installation and disassembly
6.2 Mounting types
27