Diagnostics, Faults And Warnings - Siemens SINAMICS G180 Installation And Operating Instructions Manual

Inverters - compact units, cabinet systems, cabinet units air and liquid cooled
Hide thumbs Also See for SINAMICS G180:
Table of Contents

Advertisement

Diagnostics, faults and warnings

For your personal safety and in order to prevent material damage, follow the instructions
given in section "Safety instructions" (Page 13), especially section "Information about
personal protection" (Page 16). Observe all the safety-related instructions in your product
documentation. Pay particular attention to the safety notices on the product itself.
Every converter is subject to individual inspection and warm up at the factory. Therefore
errors in the device during the initial commissioning can be almost ruled out. In most cases,
faults usually originate from the peripherals such as incorrect wiring or missing agreement
for the respective application.
The most frequent causes of errors during the initial commissioning are shown below:
Table 11- 1
Error causes and rectification
Errors
All three LEDs on the display, i.e.
"READY", "RUN" and "FAULT" are
off (dark).
LED "READY" is lit.
LEDs "RUN" and "FAULT" are off
(dark)
The converter cannot be started.
LED "RUN" is lit.
LEDs "READY" and "FAULT" are
off (dark)
The converter / motor does not
operate satisfactorily.
LED "FAULT" is lit.
LEDs "READY" and "RUN" are off
(dark)
Installation and Operating Instructions SINAMICS G180
Operating Instructions, 02/2019, 4BS0751-007
Possible causes
There is no voltage at the
converter.
The On command does not
arrive.
The On command you se-
lected is not preselected.
-
-
-
-
Fault rectification
Measure the control voltage at -X5 (see the order-
specific customer documentation)
Trace the path to the converter.
Check the parameter assignment.
Has the "Local" or "Remote" option been configured
correctly?
Have you performed the commissioning according to
the "Commissioning" (Page 115) section?
Perform the "Auto-Tuning" again.
The error message is shown on the display in plain
text. You can also invoke the event log. For additional
information, refer to the section titled "Reading event
log" (Page 188).
Siemens provides a list with all messages which are
shown on the display and possible remedies on the
Internet.