5.2 PRODUCT SETUP
The fourth current input in a bank is called IG, and the fourth voltage input in a bank is called VX. For example, F2-IB desig-
nates the IB signal on terminal 2 of the CT/VT module in slot F.
If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will
appear.

PATH: SETTINGS
PRODUCT SETUP
 DATA LOGGER
5
The data logger samples and records up to 16 analog parameters at a user-defined sampling rate. This recorded data may
be downloaded to EnerVista UR Setup and displayed with parameters on the vertical axis and time on the horizontal axis.
All data is stored in non-volatile memory, meaning that the information is retained when power to the relay is lost.
For a fixed sampling rate, the data logger can be configured with a few channels over a long period or a larger number of
channels for a shorter period. The relay automatically partitions the available memory between the channels in use. Exam-
ple storage capacities for a system frequency of 60 Hz are shown in the following table.
5-74


DATA LOGGER

DATA LOGGER MODE:
Continuous
DATA LOGGER TRIGGER:
MESSAGE
Off
DATA LOGGER RATE:
MESSAGE
60000 ms
DATA LOGGER CHNL
MESSAGE
Off
DATA LOGGER CHNL
MESSAGE
Off
DATA LOGGER CHNL
MESSAGE
Off
DATA LOGGER CHNL 16:
MESSAGE
Off
DATA LOGGER CONFIG:
MESSAGE
0 CHNL x
C60 Breaker Protection System
Range: Continuous, Trigger
Range: FlexLogic operand
Range: 15 to 3600000 ms in steps of 1
Range: Off, any FlexAnalog parameter. See Appendix A:
1:
FlexAnalog Parameters for complete list.
Range: Off, any FlexAnalog parameter. See Appendix A:
2:
FlexAnalog Parameters for complete list.
Range: Off, any FlexAnalog parameter. See Appendix A:
3:
FlexAnalog Parameters for complete list.
Range: Off, any FlexAnalog parameter. See Appendix A:
FlexAnalog Parameters for complete list.
Range: Not applicable - shows computed data only
0.0 DAYS
5 SETTINGS
5.2.9 DATA LOGGER
GE Multilin