Troubleshooting

4.4 Extended Status Words

Bit
Hex
0
1
1
2
2
4
4
4
3
8
4
10
5
20
6
40
7
80
8
100
9
200
10
400
11
800
12
1000
13
2000
14
4000
15
8000
16
10000
17
20000
18
40000
19
80000
20
100000
21
200000
22
400000
23
800000
24
1000000
25
2000000
26
4000000
27
8000000
28
10000000
29
20000000
30
40000000
31
80000000
84
VLT
16-94 Ext.
16-95 Ext. Status
Dec
Status Word
1
Ramping
2
AMA running
4
Start CW/CCW
8
0
16
0
Feedback
32
high
64
Feedback low
Output
128
current high
Control Ready
Output
256
current low
Drive Ready
Output
frequency
512
high
Output
1024
frequency low
2048
0
4096
0
Freeze Output
8192
Braking
16384
0
Freeze Output
32768
OVC active
Jog Request
65536
AC brake
131072
0
Start request
262144
0
Reference
524288
high
1048576
Reference low
Local Ref./
2097152
Remote Ref.
4194304
0
Sleep boost
8388608
0
16777216
0
33554432
0
67108864
0
External Interlock
Firemodelimi-
134217728
0
268435456
0
FlyStart Active
536870912
0
1073741824
0
Database
2147483648
busy
®
HVAC Basic Drive FC 101 Programming Guide

4.5 List of Warnings and Alarms

WARNING/ALARM 2, Live zero error
This warning or alarm will only appear if programmed by
Word 2
the user in 6-01 Live Zero Timeout Function. The signal on
Off
one of the analog inputs is less than 50% of the minimum
Hand/Auto
value programmed for that input. This condition can be
0
caused by broken wiring or faulty device sending the
0
signal.
0
Troubleshooting:
Check connections on all the analog input
0
terminals. Control card terminals 53 and 54 for
0
signals, terminal 55 common.
Check that the frequency converter programming
match the analog signal type.
WARNING/ALARM 4, Mains phase loss
A phase is missing on the supply side, or the mains
voltage imbalance is too high. This message also appears
Quick Stop
for a fault in the input rectifier on the frequency converter.
Options are programmed at 14-12 Function at Mains
DC Brake
Imbalance.
Stop
Troubleshooting:
0
Check the supply voltage and supply currents to
the frequency converter.
Request
WARNING/ALARM 7, DC overvoltage
If the intermediate circuit voltage exceeds the limit, the
frequency converter trips after a time.
Jog
Troubleshooting:
Start
Extend the ramp time
Activate functions in 2-10 Brake Function
0
WARNING/ALARM 8, DC under voltage
Start Delay
If the intermediate circuit voltage (DC) drops below the
under voltage limit, the frequency converter trips after a
Sleep
fixed time delay. The time delay varies with unit size.
Troubleshooting:
Running
Check that the supply voltage matches the
Bypass
frequency converter voltage.
Fire Mode
Perform Input voltage test
WARNING/ALARM 9, Inverter overloaded
texceed
The frequency converter is about to cut out because of an
overload (too high current for too long). The counter for
0
electronic, thermal inverter protection gives a warning at
0
90% and trips at 100%, while giving an alarm. The
frequency converter cannot be reset until the counter is
0
below 90%.
The fault is that the frequency converter is overloaded by
more than 100% for too long.
MG18B302 - Rev. 2013-09-02