Danfoss VLT HVAC Basic Drive FC 101 Programming Manual page 43

Hide thumbs Also See for VLT HVAC Basic Drive FC 101:
Table of Contents

Advertisement

Parameters
5-12 Terminal 27 Digital Input
Parameter for configuring the input function on input terminal
27.
Option:
[0]
No operation
[1]
Reset
[2]
Coast inverse
[3]
Coast and reset inverse
[4]
Quick stop inverse
[5]
DC-brake inverse
[6]
Stop inverse
[7]
External Interlock
[8]
Start
[9]
Latched start
[10]
Reversing
[11]
Start reversing
[14]
Jog
[16]
Preset ref bit 0
[17]
Preset ref bit 1
[18]
Preset ref bit 2
[19]
Freeze reference
[20]
Freeze output
[21]
Speed up
[22]
Speed down
[23]
Set-up select bit 0
[34]
Ramp bit 0
[37]
Fire Mode
[52]
Run permissive
[53]
Hand start
[54]
Auto start
[60]
Counter A (up)
[61]
Counter A (down)
[62]
Reset Counter A
[63]
Counter B (up)
[64]
Counter B (down)
[65]
Reset Counter B
5-13 Terminal 29 Digital Input
Parameter for configuring the input function on input terminal
29.
Option:
[0]
No operation
[1]
Reset
[2]
Coast inverse
[3]
Coast and reset inverse
[4]
Quick stop inverse
[5]
DC-brake inverse
[6]
Stop inverse
[7]
External Interlock
[8]
Start
[9]
Latched start
[10]
Reversing
[11]
Start reversing
[14]
Jog
*
®
VLT
HVAC Basic Drive FC 101 Programming Guide
5-13 Terminal 29 Digital Input
Parameter for configuring the input function on input terminal
29.
Function:
Option:
[16]
[17]
[18]
[19]
[20]
[21]
[22]
[23]
[32]
[34]
[37]
[52]
[53]
[54]
[60]
[61]
[62]
[63]
[64]
[65]
3.6.3 5-3* Digital Outputs
Parameters for configuring the output functions for the
output terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in 5-01 Terminal 27 Mode and set the I/O
function for terminal 29 in 5-02 Terminal 29 Mode.
NOTICE
These parameters cannot be adjusted
while the motor is running.
[0]
No operation
Function:
[1]
Control ready
[2]
Drive ready
[3]
Drive ready /
remote control
[4]
Stand-by / no
warning
[5]
Running
MG18B302 - Rev. 2013-09-02
Preset ref bit 0
Preset ref bit 1
Preset ref bit 2
Freeze reference
Freeze output
Speed up
Speed down
Set-up select bit 0
Pulse input
Ramp bit 0
Fire Mode
Run permissive
Hand start
Auto start
Counter A (up)
Counter A (down)
Reset Counter A
Counter B (up)
Counter B (down)
Reset Counter B
The digital outputs can be programmed
with these functions:
Default for all digital outputs and relay
outputs
The control board receives supply
voltage.
The frequency converter is ready for
operation and applies a supply signal on
the control board.
The frequency converter is ready for
operation and is in Auto On mode.
The frequency converter is ready for
operation. No start or stop command is
been given (start/disable). There are no
warnings.
The motor is running.
Function:
3
3
41