Parameters
16-11 Power [hp]
Range:
Function:
0 hp
[0 - 1000
View the DC link power in hp. The value
*
hp]
shown is calculated on the basis of the
actual motor voltage and motor current.
16-12 Motor Voltage
Range:
Function:
0 V
[0 - 65535 V] View the motor voltage, a calculated value
*
used for controlling the motor.
16-13 Frequency
Range:
Function:
0 Hz
[0 - 6553.5 Hz] View the motor frequency, without
*
resonance dampening.
16-14 Motor current
Range:
Function:
0 A
[0 - 655.35 A] View the motor current measured as a
*
mean value, IRMS.
16-15 Frequency [%]
Range:
Function:
0 %
[0 - 6553.5
View a 2-byte word reporting the actual
*
%]
motor frequency (without resonance
dampening) as a percentage (scale
0000-4000 Hex) of 4-19 Max Output
Frequency.
16-18 Motor Thermal
Range:
Function:
0 %
[0 -
View the calculated motor temperature in
*
100 %]
percentage of allowed maximum. At 100% a trip
will occur, if selected in 1-90 Motor Thermal
Protection. The basis for the calculation is the ETR
function selected in 1-90 Motor Thermal
Protection.
3.12.3 16-3* Drive Status
16-30 DC Link Voltage
Range:
0 V
[0 - 65535 V]
*
16-34 Heatsink Temp.
Range:
Function:
0 °C
[-128 - 127 °C] View the heat sink temperature of the
*
frequency converter.
16-35 Inverter Thermal
Range:
Function:
0 %
[0 - 255 %] View the percentage of thermal load on the
*
frequency converter. At 100% a trip occurs.
®
VLT
HVAC Basic Drive FC 101 Programming Guide
Function:
View a measured value.
MG18B302 - Rev. 2013-09-02
16-36 Inv. Nom. Current
Range:
Function:
0 A
[0 - 655.35
View the inverter nominal current, which
*
A]
should match the nameplate data on the
connected motor. The data are used for
motor protection, etc.
16-37 Inv. Max. Current
Range:
Function:
0 A
[0 - 655.35 A] View the inverter maximum current. The
*
data are used for calculation of frequency
converter protection, etc.
16-38 SL Controller State
Range:
Function:
0
[0 - 20 ] View the actual state of the Smart Logic Controller
*
(SLC).
3.12.4 16-5* Ref. & Feedb.
16-50 External Reference
Range:
Function:
0 %
[-200 - 200
View the total reference, the sum of
*
%]
digital, analog, preset, bus and freeze
references.
16-52 Feedback[Unit]
Range:
0 ProcessCtrlUnit
[-4999 - 4999
*
ProcessCtrlUnit]
3.12.5 16-6* Inputs and Outputs
16-60 Digital Input
Range:
Function:
0
[0 -
View actual state of the digital inputs 18, 19, 27
*
65535 ]
and 29.
Bit 0
Unused
Bit 1
Unused
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6~15
Unused
Table 3.8 Bits Definition
3
Function:
View the feedback
resulting from the
selection of scaling in
3-02 Minimum Reference
and 3-03 Maximum
Reference.
71