Parameters
[80]
SL Digital
See 13-52 SL Controller Action. The input
Output A
will go high whenever the Smart Logic
Action [38] Set dig. out. A high is
executed. The input goes low whenever
the Smart Logic Action [32] Set dig. out. A
low is executed.
[81]
SL Digital
See 13-52 SL Controller Action. The input
Output B
goes high whenever the Smart Logic
Action [39] Set dig. out. B high is
executed. The input goes low whenever
the Smart Logic Action [33] Set dig. out. B
low is executed.
[82]
SL Digital
See 13-52 SL Controller Action. The input
Output C
goes high whenever the Smart Logic
Action [40] Set dig. out. C high is
executed. The input goes low whenever
the Smart Logic Action [34] Set dig. out. C
low is executed.
[83]
SL Digital
See 13-52 SL Controller Action. The input
Output D
goes high whenever the Smart Logic
Action [41] Set dig. out. D high is
executed. The input goes low whenever
the Smart Logic Action [35] Set dig. out.
D low is executed.
[84]
SL Digital
See 13-52 SL Controller Action. The input
Output E
goes high whenever the Smart Logic
Action [42] Set dig. out. E high is
executed. The input goes low whenever
the Smart Logic Action [36] Set dig. out. E
low is executed.
[85]
SL Digital
See 13-52 SL Controller Action. The input
Output F
goes high whenever the Smart Logic
Action [43] Set dig. out. F high is
executed. The input goes low whenever
the Smart Logic Action [37] Set dig. out. F
low is executed.
[160] No alarm
The output is high when no alarm is
present.
[161] Running reverse The output is high when the frequency
converter runs counter clockwise (the
logical product of the status bits
'running' AND 'reverse').
[165] Local reference
The output is high when 3-13 Reference
active
Site = [2] Local or when 3-13 Reference
Site = [0] Linked to hand auto at the
same time as the LCP is in [Hand On]
mode.
[166] Remote
The output is high when 3-13 Reference
reference active
Site [1] or Linked to hand/auto [0] while
the LCP is in [Auto on] mode.
[167] Start command
The output is high when there is an
active
active Start command (i.e. via digital
input bus connection or [Hand on] or
[Auto on], and no Stop command is
active.
[168] Drive in hand
The output is high when the frequency
mode
converter is in Hand on mode (as
®
VLT
HVAC Basic Drive FC 101 Programming Guide
[169] Drive in auto
mode
[180] Clock Fault
[181] Preventive
Maintenance
[193] Sleep Mode
[194] Broken Belt
[196] Fire Mode
5-33 Term X30/7 Digi Out (MCB 101)
Option:
[0]
No
*
operation
5-34 On delay, Terminal 42 Digital Output
Range:
0.01 s
*
5-35 Off delay, Terminal 42 Digital Output
Range:
0.01 s
*
3.6.4 5-4* Relays
Parameters for configuring the timing and the output
functions for the relays.
5-40 Function Relay
Array (Relay 1 [0], Relay 2 [1])
Select options to define the function of the relays.
The selection of each mechanical relay is realised in an array
parameter.
Option:
[0]
No operation
[1]
Control Ready
[2]
Drive ready
MG18B302 - Rev. 2013-09-02
indicated by the LED light above [Hand
on].
The output is high when the frequency
converter is in Hand on mode (as
indicated by the LED light above [Auto
on].
The clock function has been reset to
default (2000-01-01) because of a power
failure.
One or more of the Preventive
Maintenance Events programmed in
23-10 Maintenance Item has passed the
time for the specified action in
23-11 Maintenance Action.
The frequency converter/system has
turned into sleep mode. See parameter
group 22-4* Sleep Mode.
A Broken Belt condition has been
detected. This function must be enabled
in 22-60 Broken Belt Function.
The frequency converter is operating in
Fire Mode. See parameter group 24-0*
Fire Mode.
Function:
This parameter is active when option module
MCB 101 is mounted in the frequency
converter. Same options and functions as
parameter group 5-3* Digital Outputs.
Function:
[0.00-600.00 s]
Function:
[0.00-600.00 s]
Function:
Default for both relays
Control board receives supply voltage.
Frequency converter is ready for
operation and applies supply signal on
control board.
3
3
43