Parameters
6-72 Terminal 45 Digital Output
Option:
3
3
[0]
No operation
*
[1]
Control Ready
[2]
Drive ready
[3]
Drive ready/remote control
[4]
Standby / no warning
[5]
Drive running
[6]
Running / no warning
[7]
Run in range/no warning
[8]
Run on ref/no warning
[9]
Alarm
[10]
Alarm or warning
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[16]
Below speed, low
[17]
Above speed, high
[19]
Below feedback, low
[20]
Above feedback, high
[21]
Thermal warning
[22]
Ready, no thermal warning
[23]
Remote, ready, no thermal warning
[24]
Ready, Voltage OK
[25]
Reverse
[26]
Bus OK
[35]
External Interlock
[36]
Control word bit 11
[37]
Control word bit 12
[41]
Below reference, low
[42]
Above ref, high
[45]
Bus Control
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital output A
[81]
SL digital output B
50
®
VLT
HVAC Basic Drive FC 101 Programming Guide
6-72 Terminal 45 Digital Output
Function:
Option:
Select the function of
[82]
Terminal 45 as a
[83]
digital current output.
[160] No alarm
See also 6-70 Terminal
[161] Running reverse
45 Mode. See
[165] Local ref. active
5-40 Function Relay for
[166] Remote ref. active
description of the
[167] Start command activ
choices.
[168] Drive in hand mode
[169] Drive in auto mode
[193] Sleep Mode
[194] Broken Belt Function
[196] Fire Mode
[198] Drive Bypass
6-73 Terminal 45 Output Min Scale
Range:
0 %
0.0%
6-74 Terminal 45 Output Max Scale
Range:
100 %
100.0%
6-76 Terminal 45 Output Bus Control
Range:
0
*
MG18B302 - Rev. 2013-09-02
SL digital output C
SL digital output D
Function:
[0 - 200 %]
Scale for the minimum output (0 or 4 mA)
*
of the analogue signal at Terminal 45. Set
the value to be the percentage of the full
range of the variable selected in
6-71 Terminal 45 Analog Output.
[0.0-200.0%]
*
Function:
[0 - 200 %]
Scale for the maximum output (20 mA)
*
of the analog signal at Terminal 45. Set
the value to be the percentage of the
full range of the variable selected in
6-71 Terminal 45 Analog Output.
Current
(mA)
20
0/4
0%
Analogue
output
Min Scale
par. 6-73
Illustration 3.11 Output Max Scale
*
[0.0-200.0%]
[0 - 16384 ]
Function:
Analogue
Variable
100%
Output
for
Max Scale
output
par. 6-74
example:
Power
Function: