Parameters
3-16 Reference 2 Source
Option:
Function:
Select the input to be used for the
second reference signal. 3-15 Reference 1
Source, 3-16 Reference 2 Source and
3-17 Reference 3 Source define up to
three different reference signals. The
sum of these reference signals defines
the actual reference. See also
1-93 Thermistor Source.
[0]
No function
[1]
Analog in 53
[2]
Analog in 54
*
[7]
Pulse input 29
[11] Local bus
reference
3-17 Reference 3 Source
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Select the reference input to be used for
the third reference signal. 3-15 Reference 1
Source, 3-16 Reference 2 Source and
3-17 Reference 3 Source define up to 3
different reference signals. The sum of
these reference signals defines the actual
reference.
The option [1] PM is not accessible, if
3-17 Reference 3 Source = [1] PM.
[0]
No function
[1]
Analog in 53
[2]
Analog in 54
[7]
Pulse input 29
[11]
Local bus
*
reference
®
VLT
HVAC Basic Drive FC 101 Programming Guide
3.4.3 3-4* Ramp 1
Configure the ramp parameter, ramping times, for each of
the 2 ramps (parameter group 3-4* Ramp 1 and parameter
group 3-5* Ramp 2).
Illustration 3.6 Ramps
3-41 Ramp 1 Ramp Up Time
Range:
Size
related
*
3-42 Ramp 1 Ramp Down Time
Range:
Size
related
*
MG18B302 - Rev. 2013-09-02
RPM
P 4-14
High-limit
Reference
P 1-23
Motor
frequency
P 4-12
Low limit
P 3-*1
Ramp (X)Up
Time (Acc)
t
acc
Function:
[0.05
Enter acceleration time from 0 Hz to
- 3600
1-23 Motor Frequency if Asynchronous
s]
motor is selected. Enter acceleration time
from 0 RPM, to 1-25 Motor Nominal Speed if
PM motor is selected. Select a ramp-up
time such that the output current does not
exceed the current limit in 4-18 Current
Limit during ramping. See ramp down time
in 3-42 Ramp 1 Ramp Down Time.
Function:
[0.05
Enter deceleration time from 1-23 Motor
- 3600
Frequency to 0 Hz if Asynchronous motor is
s]
selected. Enter deceleration time from
1-25 Motor Nominal Speed to 0 RPM if PM
motor is selected. Choose a ramp-up time
such that the output current does not
exceed the current limit in 4-18 Current
Limit Current Limit during ramping. See
ramp-up time in 3-41 Ramp 1 Ramp Up
Time.
3
3
Time
P 3-*2
Ramp (X)
Down
Time (Dec)
t
dec
33