Chapter 4 Connection and Settings
4.1 Setting the ETERNUS DX/AF
■
ETERNUS DX80 S2/DX90 S2
This section explains the setting items on the power synchronization setting screen for the ETERNUS DX80 S2/
DX90 S2.
Figure 4.3 ETERNUS DX80 S2/DX90 S2 setup (Setup Power Management screen)
•
Enable
Select the controllers (CM#0 and/or CM#1) of the ETERNUS DX80 S2/DX90 S2 that are connected to the
power synchronized unit with the RS232C cable.
Select "CM#0" when the power synchronized unit is connected to the PWC port on controller 0. Select
"CM#1" when the power synchronized unit is connected to the PWC port on controller 1.
When different power synchronized units are connected to controller 0 and controller 1 in a duplicated
configuration, select both "CM#0" and "CM#1".
•
Delay until Shutdown (min.)
Do not change the default setting (0 minute).
•
Set management unit interface
Select "Power Synchronized Unit".
•
Power Failure Signal
"Positive" (positive logic) is automatically set.
•
Low Battery Signal
"Negative" (negative logic) is automatically set.
•
UPS Shutdown Signal
Do not select the "Enable" checkbox.
"Positive" (positive logic) is set by default.
•
Auto Power
Select "Disable".
•
Power Resume
Select "Disable".
FUJITSU Storage ETERNUS DX, ETERNUS AF Configuration Guide (Power Synchronized Unit)
48
Copyright 2017 FUJITSU LIMITED
P3AM-8012-10ENZ0