Chapter 4 Connection and Settings
4.1 Setting the ETERNUS DX/AF
■
ETERNUS DX60 S2
This section explains the setting items on the power synchronization setting screen for the ETERNUS DX60 S2.
Figure 4.4 ETERNUS DX60 S2 setup (Setup Power Management screen)
•
Enable
Select the controllers (CM#0 and/or CM#1) of the ETERNUS DX60 S2 that are connected to the power
synchronized unit with the RS232C cable. Select "CM#0" when the power synchronized unit is connected to
the PWC port on controller 0. Select "CM#1" when the power synchronized unit is connected to the PWC port
on controller 1.
When different power synchronized units are connected to controller 0 and controller 1 in a duplicated
configuration, select both "CM#0" and "CM#1".
•
Delay until Shutdown (min.)
Do not change the default setting (0 minute).
•
Set management unit interface
Select "Power Synchronized Unit".
•
Power Failure Signal
"Positive" (positive logic) is automatically set.
•
Low Battery Signal
"Negative" (negative logic) is automatically set.
•
UPS Shutdown Signal
Do not select the "Enable" checkbox.
"Positive" (positive logic) is set by default.
FUJITSU Storage ETERNUS DX, ETERNUS AF Configuration Guide (Power Synchronized Unit)
49
Copyright 2017 FUJITSU LIMITED
P3AM-8012-10ENZ0