3.1 DESCRIPTION
To properly remove a module, the ejector/inserter clips, located at the top and bottom of each module, must be pulled
simultaneously. Before performing this action, control power must be removed from the relay. Record the original loca-
tion of the module to ensure that the same or replacement module is inserted into the correct slot. While modules with cur-
rent input provide automatic shorting of external CT circuits, for CT/VT modules it is recommended to short/isolate external
circuits accordingly for maximum safety.
To properly insert a module, ensure that the correct module type is inserted into the correct slot position. The ejector/
inserter clips located at the top and at the bottom of each module must be in the disengaged position as the module is
smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the clips simultaneously.
When the clips have locked into position, the module will be fully inserted.
All CPU modules except the 9E are equipped with 10/100Base-T or 100Base-F Ethernet connectors. These con-
nectors must be individually disconnected from the module before it can be removed from the chassis.
NOTE
3
The 4.0x release of the B30 relay includes new hardware modules.The new CPU modules are specified with codes
9E and higher. The new CT/VT modules are specified with the codes 8F and higher.
NOTE
The new CT/VT modules can only be used with new CPUs; similarly, old CT/VT modules can only be used with old
CPUs. To prevent hardware mismatches, the new modules have blue labels and a warning sticker stating "Attn.:
Ensure CPU and DSP module label colors are the same!". In the event that there is a mismatch between the
CPU and CT/VT module, the relay will not function and a
played.
All other input and output modules are compatible with the new hardware. Firmware versions 4.0x and higher are
only compatible with the new hardware modules. Previous versions of the firmware (3.4x and earlier) are only com-
patible with the older hardware modules.
X
W
V
c
Tx1
Rx1
Tx1
Tx2
Rx2
Tx2
Optional
Optional
direct
contact
input/output
input/output
module
module
3-8
B30
Bus Differential Relay
GE Multilin
Technical Support:
Tel: (905) 294-6222
http://www.GEmultilin.com
Fax: (905) 201-2098
U
T
S
R
P
b
a
c
b
a
c
b
a
Optional
Optional
CT/VT or
contact
contact
input/output
input/output
module
module
Figure 3–10: REAR TERMINAL VIEW
Do not touch any rear terminals while the relay is energized!
B30 Bus Differential System
or
DSP ERROR
Model:
RATINGS:
Mods:
Control Power:
88-300V DC @ 35W / 77-265V AC @ 35VA
Wiring Diagram:
Contact Inputs:
300V DC Max 10mA
Inst. Manual:
Contact Outputs:
Standard Pilot Duty / 250V AC 7.5A
Serial Number:
360V A Resistive / 125V DC Break
Firmware:
4A @ L/R = 40mS / 300W
Mfg. Date:
Made in
®
Canada
®
-
M
A
N
M
L
K
J
H
c
b
a
c
b
a
Optional
Optional
CT/VT or
contact
contact
input/output
input/output
module
module
3 HARDWARE
error will be dis-
HARDWARE MISMATCH

3.1.3 REAR TERMINAL LAYOUT

B30H00HCHF8HH6HM8AP6AU8AW6H
000
836716
D
MAZB98000029
D
2006/01/05
A
B
9
7
0
0
0
0
9
9
-
G
F
D
B
c
b
a
b
a
1
1
2
2
3
Tx1
3
4
4
Rx1
CH1
Tx
Rx
CH2
IN
Tx2
OUT
Rx2
CT/VT
CPU module
Power
module
supply
module
836772A3.CDR
b
a
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents