5.7 CONTROL ELEMENTS
COUNTER 1 UNITS: Assigns a label to identify the unit of measure pertaining to the digital transitions to be counted.
The units label will appear in the corresponding actual values status.
COUNTER 1 PRESET: Sets the count to a required preset value before counting operations begin, as in the case
where a substitute relay is to be installed in place of an in-service relay, or while the counter is running.
COUNTER 1 COMPARE: Sets the value to which the accumulated count value is compared. Three FlexLogic™ output
operands are provided to indicate if the present value is 'more than (HI)', 'equal to (EQL)', or 'less than (LO)' the set
value.
COUNTER 1 UP: Selects the FlexLogic™ operand for incrementing the counter. If an enabled UP input is received
when the accumulated value is at the limit of +2,147,483,647 counts, the counter will rollover to –2,147,483,648.
COUNTER 1 DOWN: Selects the FlexLogic™ operand for decrementing the counter. If an enabled DOWN input is
received when the accumulated value is at the limit of –2,147,483,648 counts, the counter will rollover to
+2,147,483,647.
COUNTER 1 BLOCK: Selects the FlexLogic™ operand for blocking the counting operation. All counter operands are
blocked.
CNT1 SET TO PRESET: Selects the FlexLogic™ operand used to set the count to the preset value. The counter will
be set to the preset value in the following situations:
1.
When the counter is enabled and the
and
CNT1 SET TO PRESET
2.
When the counter is running and the
changing from 1 to 0 while the counter is running has no effect on the count).
PRESET
3.
When a reset or reset/freeze command is sent to the counter and the
5
1 (when a reset or reset/freeze command is sent to the counter and the
value 0, the counter will be set to 0).
COUNTER 1 RESET: Selects the FlexLogic™ operand for setting the count to either "0" or the preset value depending
on the state of the
COUNTER 1 FREEZE/RESET: Selects the FlexLogic™ operand for capturing (freezing) the accumulated count value
into a separate register with the date and time of the operation, and resetting the count to "0".
COUNTER 1 FREEZE/COUNT: Selects the FlexLogic™ operand for capturing (freezing) the accumulated count value
into a separate register with the date and time of the operation, and continuing counting. The present accumulated
value and captured frozen value with the associated date/time stamp are available as actual values. If control power is
interrupted, the accumulated and frozen values are saved into non-volatile memory during the power down operation.
5-150
CNT1 SET TO PRESET
operand is 0, the counter will be set to 0).
CNT1 SET TO PRESET
operand.
CNT1 SET TO PRESET
B30 Bus Differential System
operand has the value 1 (when the counter is enabled
operand changes the state from 0 to 1 (
CNT1 SET TO PRESET
CNT1 SET TO PRESET
5 SETTINGS
CNT1 SET TO
operand has the value
operand has the
GE Multilin