5.2 PRODUCT SETUP
which all Modbus slave devices listen to. Addresses do not have to be sequential, but no two devices can have the same
address or conflicts resulting in errors will occur. Generally, each device added to the link should use the next higher
address starting at 1. Refer to Appendix B for more information on the Modbus protocol.
Changes to the
NOTE
e) DNP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 DNP PROTOCOL
5
5-16
setting do not take effect until the B30 is restarted.
MODBUS TCP PORT NUMBER

COMMUNICATIONS
 DNP CHANNELS
DNP ADDRESS:
MESSAGE
1
 DNP NETWORK
MESSAGE
 CLIENT ADDRESSES
DNP TCP/UDP PORT
MESSAGE
NUMBER: 20000
DNP UNSOL RESPONSE
MESSAGE
FUNCTION: Disabled
DNP UNSOL RESPONSE
MESSAGE
TIMEOUT: 5 s
DNP UNSOL RESPONSE
MESSAGE
MAX RETRIES: 10
DNP UNSOL RESPONSE
MESSAGE
DEST ADDRESS: 1
DNP CURRENT SCALE
MESSAGE
FACTOR: 1
DNP VOLTAGE SCALE
MESSAGE
FACTOR: 1
DNP POWER SCALE
MESSAGE
FACTOR: 1
DNP ENERGY SCALE
MESSAGE
FACTOR: 1
DNP PF SCALE
MESSAGE
FACTOR: 1
DNP OTHER SCALE
MESSAGE
FACTOR: 1
DNP CURRENT DEFAULT
MESSAGE
DEADBAND: 30000
DNP VOLTAGE DEFAULT
MESSAGE
DEADBAND: 30000
DNP POWER DEFAULT
MESSAGE
DEADBAND: 30000
DNP ENERGY DEFAULT
MESSAGE
DEADBAND: 30000
DNP PF DEFAULT
MESSAGE
DEADBAND: 30000
B30 Bus Differential System

DNP PROTOCOL
Range: see sub-menu below
Range: 0 to 65519 in steps of 1
Range: see sub-menu below
Range: 1 to 65535 in steps of 1
Range: Enabled, Disabled
Range: 0 to 60 s in steps of 1
Range: 1 to 255 in steps of 1
Range: 0 to 65519 in steps of 1
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000,
100000
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1
Range: 0 to 100000000 in steps of 1