Advertisement

5 SETTINGS
ETT NG
GROUND IOC1
FUNCTION:
Disabled = 0
Enabled = 1
ETT NG
GROUND IOC1
SOURCE:
IG
ETT NG
GROUND IOC1
BLOCK:
Off = 0

PATH: SETTINGS
GROUPED ELEMENTS
 BREAKER FAILURE 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
ETT NG
GROUND IOC1 PICKUP
ETT NG
DELAY:
GROUND IOC1
GROUND IOC1 RESET
PICKUP:
DELAY:
AND
RUN
t
PKP
IG ≥ PICKUP
Figure 5–54: GROUND IOC1 SCHEME LOGIC

SETTING GROUP 1(6)
BF1 FUNCTION:
Disabled
BF1 MODE:
3-Pole
BF1 SOURCE:
SRC 1
BF1 USE AMP SUPV:
Yes
BF1 USE SEAL-IN:
Yes
BF1 3-POLE INITIATE:
Off
BF1 BLOCK:
Off
BF1 PH AMP SUPV
PICKUP: 1.050 pu
BF1 N AMP SUPV
PICKUP: 1.050 pu
BF1 USE TIMER 1:
Yes
BF1 TIMER 1 PICKUP
DELAY: 0.000 s
BF1 USE TIMER 2:
Yes
BF1 TIMER 2 PICKUP
DELAY: 0.000 s
BF1 USE TIMER 3:
Yes
BF1 TIMER 3 PICKUP
DELAY: 0.000 s
BF1 BKR POS1 φA/3P:
Off
B30 Bus Differential System
5.6 GROUPED ELEMENTS
FLEXLOG C OPE AND
GROUND IOC1 PKP
GROUND IOIC DPO
GROUND IOC1 OP
t
RST
827037A4.VSD

5.6.7 BREAKER FAILURE

BREAKER FAILURE
BREAKER FAILURE 1(6)
Range: Disabled, Enabled
Range: 3-Pole, 1-Pole
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: Yes, No
Range: Yes, No
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.001 to 30.000 pu in steps of 0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic™ operand
5
5-123