APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 10 of 52)
ADDR
REGISTER NAME
Field Unit CT VT Settings (Read/Write Setting) (6 modules)
3890
Remote Phase CT x Origin 1
3891
Remote Phase CT x Origin 2
3892
Remote Ground CT x Origin 1
3893
Remote Ground CT x Origin 2
3894
AC Bank Redundancy Type
3895
Remote Phase CT 1 Primary
3896
Remote Phase CT 1 Secondary
3897
Remote Ground CT 1 Primary
3898
Remote Ground CT 1 Secondary
3899
Remote Phase VT 1 Connection
389A
Remote Phase VT 1 Secondary
389B
Remote Phase VT 1 Ratio
389D
Remote Auxiliary VT 1 Connection
389E
Remote Auxiliary VT 1 Secondary
389F
Remote Auxiliary VT 1 Ratio
38A1
...Repeated for Field Unit 2
38B2
...Repeated for Field Unit 3
38C3
...Repeated for Field Unit 4
38D4
...Repeated for Field Unit 5
38E5
...Repeated for Field Unit 6
Field Unit Contact Inputs (Read/Write Setting) (40 modules)
3900
Field Contact Input 1 ID
3906
Field Contact Input 1 Origin
3907
Field Contact Input 1 Input
3908
Field Contact Input 1 Failsafe Value
3909
Field Contact Input 1 Debounce Time
390A
Field Contact Input 1 Events
390B
...Repeated for Field Contact Input 2
3916
...Repeated for Field Contact Input 3
3921
...Repeated for Field Contact Input 4
392C
...Repeated for Field Contact Input 5
3937
...Repeated for Field Contact Input 6
3942
...Repeated for Field Contact Input 7
394D
...Repeated for Field Contact Input 8
3958
...Repeated for Field Contact Input9
3963
...Repeated for Field Contact Input 10
396E
...Repeated for Field Contact Input 11
3979
...Repeated for Field Contact Input 12
3984
...Repeated for Field Contact Input 13
398F
...Repeated for Field Contact Input 14
399A
...Repeated for Field Contact Input 15
39A5
...Repeated for Field Contact Input 16
39B0
...Repeated for Field Contact Input 17
39BB
...Repeated for Field Contact Input 18
39C6
...Repeated for Field Contact Input 19
39D1
...Repeated for Field Contact Input 20
39DC
...Repeated for Field Contact Input 21
39E7
...Repeated for Field Contact Input 22
39F2
...Repeated for Field Contact Input 23
39FD
...Repeated for Field Contact Input 24
3A08
...Repeated for Field Contact Input 25
3A13
...Repeated for Field Contact Input 26
GE Multilin
RANGE
0 to 16
0 to 16
0 to 16
0 to 16
0 to 2
1 to 65000
0 to 1
1 to 65000
0 to 1
0 to 1
25 to 240
1 to 24000
0 to 6
25 to 240
1 to 24000
---
0 to 8
1 to 18
0 to 1
0 to 16
0 to 1
B30 Bus Differential System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F247
---
1
F247
---
1
F248
---
1
F248
---
1
F261
---
1
F001
---
1
F123
---
1
F001
---
1
F123
---
1
F100
---
0.1
F001
---
1
F060
---
1
F166
---
0.1
F001
---
1
F060
---
---
F205
---
1
F256
---
1
F001
---
1
F108
ms
0.5
F001
---
1
F102
DEFAULT
0 (None)
0 (None)
0 (None)
0 (None)
B
1 (Dependability
Biased)
1
0 (1 A)
1
0 (1 A)
0 (Wye)
664
1
1 (Vag)
664
1
"FCI 1"
0 (None)
1
0 (Off)
20
1 (Enabled)
B-17

Advertisement

Table of Contents
loading