Real Time Clock - GE B30 Instruction Manual

Bus differential system, ur series
Hide thumbs Also See for B30:
Table of Contents

Advertisement

5 SETTINGS
PATH: SETTINGS
PRODUCT SETUP
 REAL TIME
 CLOCK
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The date and time can be synchronized a known time base and to other relays using an IRIG-B signal. It has the same
accuracy as an electronic watch, approximately ±1 minute per month. If an IRIG-B signal is connected to the relay, only the
current year needs to be entered. See the
The
REAL TIME CLOCK EVENTS
The
LOCAL TIME OFFSET FROM UTC
(Greenwich Mean Time) in hours. This setting has two uses. When the B30 is time synchronized with IRIG-B, or has no
permanent time synchronization, the offset is used to calculate UTC time for IEC 61850 features. When the B30 is time
synchronized with SNTP, the offset is used to determine the local time for the B30 clock, since SNTP provides UTC time.
The daylight savings time (DST) settings can be used to allow the B30 clock can follow the DST rules of the local time
zone. Note that when IRIG-B time synchronization is active, the DST settings are ignored. The DST settings are used when
the B30 is synchronized with SNTP, or when neither SNTP nor IRIG-B is used.
Only timestamps in the event recorder and communications protocols are affected by the daylight savings time set-
tings. The reported real-time clock value does not change.
NOTE
GE Multilin


REAL TIME CLOCK

IRIG-B SIGNAL TYPE:
None
REAL TIME CLOCK
EVENTS: Disabled
LOCAL TIME OFFSET
FROM UTC:
0.0 hr
DAYLIGHT SAVINGS
TIME: Disabled
DST START MONTH:
April
DST START DAY:
Sunday
DST START DAY
INSTANCE: First
DST START HOUR:
2:00
DST STOP MONTH:
January
DST STOP DAY:
Sunday
DST STOP DAY
INSTANCE: First
DST STOP HOUR:
2:00

COMMANDS
SET DATE AND TIME
setting allows changes to the date and/or time to be captured in the event record.
setting is used to specify the local time zone offset from Universal Coordinated Time
B30 Bus Differential System
5.2 PRODUCT SETUP
5.2.6 REAL TIME CLOCK
Range: None, DC Shift, Amplitude Modulated
Range: Disabled, Enabled
Range: –24.0 to 24.0 hrs in steps of 0.5
Range: Disabled, Enabled
Range: January to December (all months)
Range: Sunday to Saturday (all days of the week)
Range: First, Second, Third, Fourth, Last
Range: 0:00 to 23:00
Range: January to December (all months)
Range: Sunday to Saturday (all days of the week)
Range: First, Second, Third, Fourth, Last
Range: 0:00 to 23:00
menu to manually set the relay clock.
5
5-37

Advertisement

Table of Contents
loading

Table of Contents