Advertisement

5 SETTINGS
At 0% of pickup, the operating time equals the UNDERVOLTAGE DELAY setting.
NOTE
b) PHASE UNDERVOLTAGE (ANSI 27P)

PATH: SETTINGS
GROUPED ELEMENTS
 PHASE
 UNDERVOLTAGE1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Two undervoltage elements facilitate applications including undervoltage supervision of the main bus differential protection
to prevent maloperation in the event of CT trouble.
GE Multilin
% of voltage pickup
Figure 5–60: INVERSE TIME UNDERVOLTAGE CURVES
SETTING GROUP 1(6)
PHASE UV1
FUNCTION: Disabled
PHASE UV1 SIGNAL
SOURCE: SRC 1
PHASE UV1 MODE:
Phase to Ground
PHASE UV1
PICKUP: 1.000 pu
PHASE UV1
CURVE: Definite Time
PHASE UV1
DELAY:
1.00 s
PHASE UV1 MINIMUM
VOLTAGE: 0.100 pu
PHASE UV1 BLOCK:
Off
PHASE UV1
TARGET: Self-reset
PHASE UV1
EVENTS: Disabled
B30 Bus Differential System
5.6 GROUPED ELEMENTS
842788A1.CDR

VOLTAGE ELEMENTS
PHASE UNDERVOLTAGE1(3)
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: Phase to Ground, Phase to Phase
Range: 0.000 to 3.000 pu in steps of 0.001
Range: Definite Time, Inverse Time
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.000 to 3.000 pu in steps of 0.001
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5
5-133