B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 47 of 52)
ADDR
REGISTER NAME
CA20
...Repeated for Direct Output 9
CA22
...Repeated for Direct Output 10
CA24
...Repeated for Direct Output 11
CA26
...Repeated for Direct Output 12
CA28
...Repeated for Direct Output 13
B
CA2A
...Repeated for Direct Output 14
CA2C
...Repeated for Direct Output 15
CA2E
...Repeated for Direct Output 16
CA30
...Repeated for Direct Output 17
CA32
...Repeated for Direct Output 18
CA34
...Repeated for Direct Output 19
CA36
...Repeated for Direct Output 20
CA38
...Repeated for Direct Output 21
CA3A
...Repeated for Direct Output 22
CA3C
...Repeated for Direct Output 23
CA3E
...Repeated for Direct Output 24
CA40
...Repeated for Direct Output 25
CA42
...Repeated for Direct Output 26
CA44
...Repeated for Direct Output 27
CA46
...Repeated for Direct Output 28
CA48
...Repeated for Direct Output 29
CA4A
...Repeated for Direct Output 30
CA4C
...Repeated for Direct Output 31
CA4E
...Repeated for Direct Output 32
Direct Input/Output Alarms (Read/Write Setting)
CAD0
Direct Input/Output Channel 1 CRC Alarm Function
CAD1
Direct I/O Channel 1 CRC Alarm Message Count
CAD2
Direct Input/Output Channel 1 CRC Alarm Threshold
CAD3
Direct Input/Output Channel 1 CRC Alarm Events
CAD4
Reserved (4 items)
CAD8
Direct Input/Output Channel 2 CRC Alarm Function
CAD9
Direct I/O Channel 2 CRC Alarm Message Count
CADA
Direct Input/Output Channel 2 CRC Alarm Threshold
CADB
Direct Input/Output Channel 2 CRC Alarm Events
CADC
Reserved (4 items)
CAE0
Direct I/O Ch 1 Unreturned Messages Alarm Function
CAE1
Direct I/O Ch 1 Unreturned Messages Alarm Msg Count
CAE2
Direct I/O Ch 1 Unreturned Messages Alarm Threshold
CAE3
Direct I/O Ch 1 Unreturned Messages Alarm Events
CAE4
Reserved (4 items)
CAE8
Direct IO Ch 2 Unreturned Messages Alarm Function
CAE9
Direct I/O Ch 2 Unreturned Messages Alarm Msg Count
CAEA
Direct I/O Ch 2 Unreturned Messages Alarm Threshold
CAEB
Direct I/O Channel 2 Unreturned Messages Alarm Events
CAEC
Reserved (4 items)
Remote Devices (Read/Write Setting) (32 modules)
CB00
Remote Device 1 GSSE/GOOSE Application ID
CB21
Remote Device 1 GOOSE Ethernet APPID
CB22
Remote Device 1 GOOSE Dataset
CB23
Remote Device 1 in PMU Scheme
CB24
...Repeated for Device 2
CB48
...Repeated for Device 3
CB6C
...Repeated for Device 4
CB90
...Repeated for Device 5
B-54
RANGE
0 to 1
100 to 10000
1 to 1000
0 to 1
1 to 1000
0 to 1
100 to 10000
1 to 1000
0 to 1
1 to 1000
0 to 1
100 to 10000
1 to 1000
0 to 1
1 to 1000
0 to 1
100 to 10000
1 to 1000
0 to 1
1 to 1000
---
0 to 16383
0 to 8
0 to 1
B30 Bus Differential System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F102
---
1
F001
---
1
F001
---
1
F102
---
1
F001
---
1
F102
---
1
F001
---
1
F001
---
1
F102
---
1
F001
---
1
F102
---
1
F001
---
1
F001
---
1
F102
---
1
F001
---
1
F102
---
1
F001
---
1
F001
---
1
F102
---
1
F001
---
---
F209
"Remote Device 1"
---
1
F001
---
1
F184
---
1
F126
DEFAULT
0 (Disabled)
600
10
0 (Disabled)
10
0 (Disabled)
600
10
0 (Disabled)
10
0 (Disabled)
600
10
0 (Disabled)
10
0 (Disabled)
600
10
0 (Disabled)
10
0
0 (Fixed)
0 (No)
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents