5.2 PRODUCT SETUP
PATH: SETTINGS
PRODUCT SETUP
ANALOG INPUT / MME
POINTS
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A: FlexAnalog Parameters for the
full range of assignable parameters.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first "Off" value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first "Off" point are ignored.
NOTE
Changes to the DNP / IEC 60870-5-104 point lists take effect when the B30 is restarted.
NOTE
g) IEC 61850 PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
IEC 61850 PROTOCOL
5
The B30 Bus Differential System is provided with optional IEC 61850 communications capability. This fea-
ture is specified as a software option at the time of ordering. Refer to the Ordering section of chapter 2 for
additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
5-20
COMMUNICATIONS
Point:
Off
Point:
MESSAGE
Off
Point:
MESSAGE
Off
COMMUNICATIONS
GSSE / GOOSE
CONFIGURATION
SERVER
MESSAGE
CONFIGURATION
IEC 61850 LOGICAL
MESSAGE
NODE NAME PREFIXES
MMXU DEADBANDS
MESSAGE
GGIO1 STATUS
MESSAGE
CONFIGURATION
GGIO2 CONTROL
MESSAGE
CONFIGURATION
GGIO4 ANALOG
MESSAGE
CONFIGURATION
GGIO5 UINTEGER
MESSAGE
CONFIGURATION
REPORT CONTROL
MESSAGE
CONFIGURATION
XCBR
MESSAGE
CONFIGURATION
XSWI
MESSAGE
CONFIGURATION
B30 Bus Differential System
DNP / IEC104 POINT LISTS
Range: any FlexAnalog parameter
0
Range: any FlexAnalog parameter
1
↓
Range: any FlexAnalog parameter
255
IEC 61850 PROTOCOL
5 SETTINGS
ANALOG INPUT / MME POINTS
GE Multilin