GE B30 Instruction Manual page 424

Bus differential system, ur series
Hide thumbs Also See for B30:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 23 of 52)
ADDR
REGISTER NAME
5D50
...Repeated for Ground Time Overcurrent 6
Ground Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5E00
Ground Instantaneous Overcurrent 1 Signal Source
5E01
Ground Instantaneous Overcurrent 1 Function
5E02
Ground Instantaneous Overcurrent 1 Pickup
B
5E03
Ground Instantaneous Overcurrent 1 Delay
5E04
Ground Instantaneous Overcurrent 1 Reset Delay
5E05
Ground Instantaneous Overcurrent 1 Block
5E06
Ground Instantaneous Overcurrent 1 Target
5E07
Ground Instantaneous Overcurrent 1 Events
5E08
Reserved (8 items)
5E10
...Repeated for Ground Instantaneous Overcurrent 2
5E20
...Repeated for Ground Instantaneous Overcurrent 3
5E30
...Repeated for Ground Instantaneous Overcurrent 4
5E40
...Repeated for Ground Instantaneous Overcurrent 5
5E50
...Repeated for Ground Instantaneous Overcurrent 6
5E60
...Repeated for Ground Instantaneous Overcurrent 7
5E70
...Repeated for Ground Instantaneous Overcurrent 8
5E80
...Repeated for Ground Instantaneous Overcurrent 9
5E90
...Repeated for Ground Instantaneous Overcurrent 10
5EA0
...Repeated for Ground Instantaneous Overcurrent 11
5EB0
...Repeated for Ground Instantaneous Overcurrent 12
Setting Groups (Read/Write Setting)
5F80
Setting Group for Modbus Comms (0 means group 1)
5F81
Setting Groups Block
5F82
FlexLogic Operands to Activate Groups 2 through 6 (5
items)
5F89
Setting Group Function
5F8A
Setting Group Events
Setting Groups (Read Only)
5F8B
Current Setting Group
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
5F94
Setting Group 2 Name
5F9C
Setting Group 3 Name
5FA4
Setting Group 4 Name
5FAC
Setting Group 5 Name
5FB4
Setting Group 6 Name
Bus Configuration (Read/Write Setting) (2 modules)
6500
Bus Zone xA Source (6 items)
6506
Bus Zone xA Status (6 items)
650C
...Repeated for Bus Zone 2
Bus Differential (Read/Write Grouped Setting) (4 modules)
6520
Bus Zone 1 Function
6521
Bus Zone 1 Pickup
6522
Bus Zone 1 Low Slope
6523
Bus Zone 1 Low Breakpoint
6524
Bus Zone 1 High Slope
6525
Bus Zone 1 High Breakpoint
6526
Bus Zone 1 High Set
6527
Bus Zone 1 Seal In
6528
Bus Zone 1 Block
6529
Bus Zone 1 Events
652A
Bus Zone 1 Target
B-30
RANGE
0 to 5
0 to 1
0 to 30
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 5
0 to 65535
0 to 65535
0 to 1
0 to 1
0 to 5
---
---
---
---
---
---
0 to 5
0 to 65535
0 to 1
0.05 to 2
15 to 100
1 to 30
50 to 100
1 to 30
0.1 to 99.99
0 to 65.535
0 to 65535
0 to 1
0 to 2
B30 Bus Differential System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F167
---
1
F102
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F001
---
1
F300
---
1
F300
---
1
F102
---
1
F102
---
1
F001
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
---
F203
---
1
F167
---
1
F300
---
1
F102
pu
0.001
F001
%
1
F001
pu
0.01
F001
%
1
F001
pu
0.01
F001
pu
0.01
F001
s
0.001
F001
---
1
F300
---
1
F102
---
1
F109
DEFAULT
0 (SRC 1)
0 (Disabled)
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
0
0
0
0 (Disabled)
0 (Disabled)
0
(none)
(none)
(none)
(none)
(none)
(none)
0 (SRC 1)
0
0 (Disabled)
100
25
200
60
800
1500
400
0
0 (Disabled)
0 (Self-reset)
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents