5 SETTINGS
PUSHBTN 1 AUTORST DELAY: This setting specifies the time delay for automatic reset of the pushbutton when in
"Latched" mode.
PUSHBTN 1 REMOTE: This setting assigns the FlexLogic operand serving to inhibit user-programmable pushbutton
operation from the operand assigned to the
PUSHBTN 1 LOCAL: This setting assigns the FlexLogic operand serving to inhibit user-programmable pushbutton
operation from the front panel pushbuttons. This inhibit functionality is not applicable to pushbutton autoreset.
PUSHBTN 1 DROP-OUT TIME: This setting applies only to "Self-Reset" mode and specifies the duration of the user-
programmable pushbutton active status after the front panel pushbutton has been released. When activated remotely,
this setting specifies the entire activation time of the pushbutton; the length of time the operand selected by PUSHBTN
1 SET remains on has no effect on the pulse duration.
PUSHBTN 1 LED CTL: This setting assigns the FlexLogic operand serving to drive the front panel pushbutton LED. If
this setting is "Off", then LED operation is directly linked to the
PUSHBTN 1 MESSAGE: This setting controls the behavior of the user-programmable pushbutton that is programmed
in the
and
PUSHBTN 1 ID
PUSHBTN 1 ON TEXT
sage that is programmed in the
When set to "Disabled", user-programmable pushbutton messages do not display. Otherwise the on message displays
when the user-programmable pushbutton becomes activated, and if in the "Latched" mode the off message displays
when the user-programmable pushbutton becomes deactivated.
When set to "Normal", the duration the message displays is as specified by the
When set to "High Priority", the duration of the off message is as specified by the
on message is displayed as long as the user-programmable pushbutton is activated. While activated, target and other
messages are suppressed. To allow front panel keypad operation, when a keypad button is pressed the message is
supressed for 10 seconds.
PUSHBUTTON 1 EVENTS: If this setting is enabled, each user-programmable pushbutton state change is logged as
an event into the event recorder.
GE Multilin
or
PUSHBTN 1 SET
settings, and the behavior of the user-programmable pushbutton off mes-
and
PUSHBTN1 ID
PUSHBTN 1 OFF TEXT
B30 Bus Differential System
settings.
PUSHBTN 1 RESET
operand.
PUSHBUTTON 1 ON
settings.
FLASH MESSAGE TIME
FLASH MESSAGE TIME
5.2 PRODUCT SETUP
setting.
setting, but the