GE B30 Instruction Manual page 455

Bus differential system, ur series
Hide thumbs Also See for B30:
Table of Contents

Advertisement

APPENDIX B
F090
ENUMERATION: LATCHING OUTPUT TYPE
0 = Operate-dominant, 1 = Reset-dominant
F100
ENUMERATION: VT CONNECTION TYPE
0 = Wye, 1 = Delta
F101
ENUMERATION: MESSAGE DISPLAY INTENSITY
0 = 25%, 1 = 50%, 2 = 75%, 3 = 100%
F102
ENUMERATION: DISABLED/ENABLED
0 = Disabled; 1 = Enabled
F103
ENUMERATION: CURVE SHAPES
bitmask
curve shape
0
IEEE Mod Inv
1
IEEE Very Inv
2
IEEE Ext Inv
3
IEC Curve A
4
IEC Curve B
5
IEC Curve C
6
IEC Short Inv
7
IAC Ext Inv
8
IAC Very Inv
F104
ENUMERATION: RESET TYPE
0 = Instantaneous, 1 = Timed
F105
ENUMERATION: LOGIC INPUT
0 = Disabled, 1 = Input 1, 2 = Input 2
F106
ENUMERATION: PHASE ROTATION
0 = ABC, 1 = ACB
F108
ENUMERATION: OFF/ON
0 = Off, 1 = On
GE Multilin
bitmask
curve shape
9
IAC Inverse
10
IAC Short Inv
11
I2t
12
Definite Time
13
FlexCurve™ A
14
FlexCurve™ B
15
FlexCurve™ C
16
FlexCurve™ D
B30 Bus Differential System
F109
ENUMERATION: CONTACT OUTPUT OPERATION
0 = Self-reset, 1 = Latched, 2 = Disabled
F110
ENUMERATION: CONTACT OUTPUT LED CONTROL
0 = Trip, 1 = Alarm, 2 = None
F111
ENUMERATION: UNDERVOLTAGE CURVE SHAPES
0 = Definite Time, 1 = Inverse Time
F112
ENUMERATION: RS485 BAUD RATES
bitmask
value
bitmask
0
300
4
1
1200
5
2
2400
6
3
4800
7
F113
ENUMERATION: PARITY
0 = None, 1 = Odd, 2 = Even
F114
ENUMERATION: IRIG-B SIGNAL TYPE
0 = None, 1 = DC Shift, 2 = Amplitude Modulated
F115
ENUMERATION: BREAKER STATUS
0 = Auxiliary A, 1 = Auxiliary B
F116
ENUMERATION: NEUTRAL OVERVOLTAGE CURVES
0 = Definite Time, 1 = FlexCurve™ A, 2 = FlexCurve™ B,
3 = FlexCurve™ C
F117
ENUMERATION: NUMBER OF OSCILLOGRAPHY RECORDS
0 = 1×72 cycles, 1 = 3×36 cycles, 2 = 7×18 cycles, 3 = 15×9 cycles
F118
ENUMERATION: OSCILLOGRAPHY MODE
0 = Automatic Overwrite, 1 = Protected
B.4 MEMORY MAPPING
value
bitmask
value
9600
8
115200
19200
9
14400
38400
10
28800
57600
11
33600
B-61
B

Advertisement

Table of Contents
loading

Table of Contents