Configuration - Siemens SIMATIC ET 200eco PN Operating Instructions Manual

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200eco PN:
Table of Contents

Advertisement

IO-Link Master
11.2 IO-Link Master (6ES7148-6JD00-0AB0)
11.2.1

Configuration

Introduction
The IO-Link Master 4 IO-L 4×M12 has four ports. Each port is represented by a submodule.
Configuration of the IO-Link port of the IO-Link Master 4 IO-L 4×M12
You specify the various operating modes of each IO-Link port by configuring a relevant
submodule:
● as digital input by configuring a digital input submodule,
● as digital output by configuring a digital output submodule,
● as IO-Link device by configuring an IO-Link submodule.
● Port deactivated:
– In STEP 7 V5.5 and higher and with GSD: By deleting the submodule,
– in STEP 7 (TIA Portal): By deactivating the port enable.
The IO-Link ports are preconfigured as 2I + PQI.
When configuring IO-Link submodules, you can select address spaces for I/O data in the
following byte scales:
● 1 I/1 O + PQI
● 2 I + PQI
● 2 I/2 O + PQI
● 4 I/4 O + PQI
● 8 I/8 O + PQI
● 16 I/16 O + PQI
● 32 I/32 O + PQI
Note
Port Qualifier Information (PQI)
The Port Qualifier Information (PQI) with the size of 1 byte is always transferred together
with the input data of the IO-Link device. The PQI cannot be deactivated.
Additional information on the structure of the PQI byte is available in the appendix I/O
address space (Page 250).
Various parameters are available depending on the operating mode.
More information on the parameters is available in the chapter Parameter (Page 223).
222
Operating Instructions, 08/2016, A5E01250250-AJ
ET 200eco PN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents