I/O device analog input/analog output
10.2 I/O device analog output
Output range
1 to 5 V
0 to 10 V
±10 V
0 to 20 mA
4 to 20 mA
±20 mA
10.2.3

Parameter description analog output

Group diagnostics
You can generally enable and disable the diagnostics function of the device with this
parameter.
The "Fault" and "Parameter assignment error" diagnostics functions are always independent
of the group diagnostics.
Diagnostics, missing 1L+
If you enable this parameter, the check for missing supply voltage is enabled.
Diagnostics, sensor supply short circuit
When this parameter is enabled, the system generates a diagnostics event if it detects a
short-circuit of the sensor supply to ground. This diagnostics function is activated when the
group diagnostics function is enabled.
202
Permitted substitute value
0.000 V to 5.704 V
0.000 V to 11.759 V
-11.759 V to 11.759 V
0.000 mA to 23.518 mA
0.000 mA to 22.814 mA
-23.519 mA to 23.518 mA
Operating Instructions, 08/2016, A5E01250250-AJ