Technical data
Output current
•
•
Load resistance range
Lamp load
Parallel wiring of two outputs
•
•
Control of a digital input
Switching frequency
•
•
•
Limiting of the inductive shutdown voltage to
lamp load
Short-circuit protection of the output
•
* Make allowances for the maximum total current when configuring the module.
ET 200eco PN
Operating Instructions, 08/2016, A5E01250250-AJ
At signal "1"
For "0" signal (residual current)
To increase performance
For redundant control of a load
With resistive load
With inductive load
With lamp load
Response threshold
I/O device digital inputs/digital outputs
9.2 I/O device digital outputs
Max. 1.3 A
Max. 1.5 mA
22 Ω to 3.3 kΩ
Max. 5 W
No
Supported
Yes
Max. 100 Hz
Max. 0.5 Hz
Max. 1 Hz
Typ. 1L+/2L+ (-47 V)
Yes, electronic
Typ. 1.8 A (per channel)
145