Technical data
Basic error limit (operational limit at 25 °C, rela-
tive to input range)
Temperature error (relative to input range)
Linearity error (relative to input range)
Repeat accuracy (in steady-state condition at
25°C, relative to input range)
Operational limit for internal temperature sensor
Basic error limit for internal temperature sensor
Status, interrupts, diagnostics
Interrupts
Diagnostics functions
Monitoring for
Insulation
Insulation test voltage
ET 200eco PN
Operating Instructions, 08/2016, A5E01250250-AJ
3
Group error/maintenance
Bus monitoring PROFINET IO
Monitoring of supply voltage 1L+
Existing connection to bus
Analog input error
Diagnostic information can be read
Sensor supply short-circuit
Wire break
Underflow and overflow
Supply voltage 1L+
Ethernet interface
All other circuit elements
I/O device analog input/analog output
10.1 I/O device analog input
U
0.1%
I
0.1%
R, RTD
0.05%
TC
0.1%
Ambient temperature
positive
U
0.0035%/K
I
0.006%/K
R, RTD
0.0005%/K
TC
0.0035%/K
±0.01%
±0.008%
±3 °C
±2 °C
Yes
Red/yellow "SF/MT" LED
Red "BF" LED
Green "ON" LED
Green "P1 LK" and "P2 LK" LED; LED for
PROFINET IO infeed and loop-through
Red LED
Yes
Yes, only if channel is enabled
4 to 20 mA, 1 to 5 V, resistors and thermoresis-
tors
Yes
Yes
1500 V
(IEEE802.3)
rms
707 V DC (type test)
negative
0.007%/K
0.007%/K
0.001%/K
0.007%/K
161