Siemens SIMATIC ET 200eco PN M12-L System Manual

Hide thumbs Also See for SIMATIC ET 200eco PN M12-L:
Table of Contents

Advertisement

Quick Links

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIMATIC ET 200eco PN M12-L

  • Page 2 Distributed I/O system ET 200eco PN M12-L Preface ET 200eco PN M12-L Documentation Guide SIMATIC System overview Mounting ET 200eco PN Distributed I/O system ET 200eco PN M12-L Connecting Configuring System Manual Commissioning the Maintenance Technical specifications Safety-related shutdown Dimension drawings Accessories/spare parts 06/2021 A5E48753295-AC...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4: Preface

    Validity of the documentation This documentation applies to the SIMATIC ET 200eco PN M12-L distributed I/O devices. Changes compared to previous version This manual contains the following changes/additions compared to the previous version: •...
  • Page 5 Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
  • Page 6 This information is provided by the Siemens Industry Online Support in the Internet (http://www.siemens.com/automation/service&support). Industry Mall The Industry Mall is the catalog and order system of Siemens AG for automation and drive solutions on the basis of Totally Integrated Automation (TIA) and Totally Integrated Power (TIP).
  • Page 7: Table Of Contents

    Table of contents Preface ..............................3 ET 200eco PN M12-L Documentation Guide ..................8 System overview ..........................12 What are the SIMATIC ET 200eco PN M12-L distributed I/O devices? ........12 Components ........................15 Mounting ............................. 18 Basics ..........................18 Mounting without mounting rail ..................
  • Page 8 Table of contents Commissioning the ..........................53 Commissioning ET 200eco PN M12-L on PROFINET IO ............53 Startup of the I/O device ....................54 6.2.1 Unconfigured without PROFINET IO ..................54 6.2.2 Unconfigured on PROFINET IO .................... 55 6.2.3 Configured on PROFINET IO ....................56 Identification and maintenance data ..................
  • Page 9: Et 200Eco Pn M12-L Documentation Guide

    This arrangement enables you to access the specific content you require. Basic information The system manual describes in detail the configuration, installation, wiring and commissioning of the SIMATIC ET 200eco PN M12-L distributed I/O system. The STEP 7 online help supports you in the configuration and programming. Device information...
  • Page 10 You must register once to use the full functionality of "mySupport". You can find "mySupport" on the Internet (https://support.industry.siemens.com/My/ww/en). Application examples The application examples support you with various tools and examples for solving your automation tasks.
  • Page 11 You can find the SIMATIC Automation Tool on the Internet (https://support.industry.siemens.com/cs/ww/en/view/98161300). PRONETA SIEMENS PRONETA (PROFINET network analysis) allows you to analyze the plant network during commissioning. PRONETA features two core functions: • The topology overview automatically scans the PROFINET and all connected components.
  • Page 12 ET 200eco PN M12-L Documentation Guide SINETPLAN SINETPLAN, the Siemens Network Planner, supports you in planning automation systems and networks based on PROFINET. The tool facilitates professional and predictive dimensioning of your PROFINET installation as early as in the planning stage. In addition, SINETPLAN supports you during network optimization and helps you to exploit network resources optimally and to plan reserves.
  • Page 13: System Overview

    What are the SIMATIC ET 200eco PN M12-L distributed I/O devices? SIMATIC ET 200eco PN M12-L The SIMATIC ET 200eco PN M12-L distributed I/O devices are part of a scalable and highly flexible, distributed I/O system for connecting the process signals to a higher-level controller via PROFINET IO.
  • Page 14 • The easy handling of ET 200eco PN M12-L facilitates efficient commissioning and maintenance. Configuration The SIMATIC ET 200eco PN M12-L distributed I/O system is made up of the following I/O devices: • Digital inputs of the I/O device • Digital outputs of the I/O device •...
  • Page 15 System overview 2.1 What are the SIMATIC ET 200eco PN M12-L distributed I/O devices? Additional enabled functions The following table provides an overview of various functions. These functions have been enabled in addition. Table 2- 1 Overview of the supported functions...
  • Page 16: Components

    System overview 2.2 Components Components Components of the ET 200eco PN M12-L distributed I/O system The following table shows and explains the function of the most important components of the ET 200eco PN M12-L distributed I/O system. Table 2- 2 Overview of components Component Function...
  • Page 17 System overview 2.2 Components Component Function Figure Identification • The identification labels come with labels the module • They can be machine-printed • They can be ordered separately Sealing cap • Caps for unused connections • IP protection class is maintained through use PROFINET IO cable •...
  • Page 18 System overview 2.2 Components Component Function Figure Y cable • Double connection of actuators or sensors to one socket • IP protection class is maintained when 2 actuators or sensors are connected to one socket Y-connector • Double connection of actuators or sensors to one socket •...
  • Page 19: Mounting

    Mounting Basics Introduction All ET 200eco PN M12-L distributed I/O devices are designed for the degree of protection IP65/IP67. This means that you can directly mount these I/O devices in your plant. Mounting position You can mount the ET 200eco PN M12-L distributed I/O devices in any mounting position. Minimum clearances Ensure that the I/O devices are installed with a minimum clearance of 2 cm.
  • Page 20: Mounting Without Mounting Rail

    Mounting 3.2 Mounting without mounting rail Mounting without mounting rail Introduction The ET 200eco PN M12-L distributed I/O devices are designed for installation on a level, firm surface. The axially symmetric drill holes allow you to fasten the I/O devices to an aluminum or carrier profile.
  • Page 21 Mounting 3.2 Mounting without mounting rail Installing the I/O device The I/O devices have an attachment point on top and on the bottom. You can also attach the I/O devices to the side. To install the I/O device, follow these steps: 1.
  • Page 22: Mounting With Mounting Rail

    Mounting 3.3 Mounting with mounting rail Mounting with mounting rail Introduction A suitable mounting rail and profile screws are available as accessories for mounting the I/O devices. Advantages of the mounting rail: • Mounting rail can be cut to size for the application •...
  • Page 23 Mounting 3.3 Mounting with mounting rail Installing the mounting rail The mounting rail with 500 mm length must be cut to length according to your requirements. To install the mounting rail with 500 mm length, follow these steps: 1. Drill the mounting holes for screws with 8 mm diameter. We recommend that, after an initial distance of 12 mm, the mounting holes be provided at regular intervals of 182 mm.
  • Page 24: Connecting

    Connecting Rules and regulations for operation Introduction The ET 200eco PN M12-L distributed I/O devices are part of plants and systems. Depending on the area of application, follow the special rules and regulations. This section provides an overview of the most important rules to be followed for integrating the ET 200eco PN M12-L distributed I/O devices into a plant or a system.
  • Page 25 (e.g. lightning protection elements). Additional information can be found in the function manual Designing interference-free controllers (https://support.industry.siemens.com/cs/ww/en/view/59193566). • For 24 V DC supply: Ensure that there is a safe electrical separation of extra-low voltage (SELV/PELV) according to IEC 61010-2-201 or IEC 60950-1.
  • Page 26 • Configure the plant/system in such a way that an error does not result in undefined states. – Line/wire break – Cross-circuit in the line Reference Additional information can be found in the function manual Designing interference-free controllers (https://support.industry.siemens.com/cs/ww/en/view/59193566). Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...
  • Page 27: Operation On Grounded/Non-Grounded Infeed

    Connecting 4.2 Operation on grounded/non-grounded infeed Operation on grounded/non-grounded infeed Introduction Information is provided below on the overall configuration of an ET 200eco PN M12-L distributed I/O system on a grounded incoming supply (TN-S network). The specific subjects discussed are: •...
  • Page 28 Connecting 4.2 Operation on grounded/non-grounded infeed Configuring ET 200eco PN M12-L with grounded reference potential (PELV) When configuring the ET 200eco PN M12-L distributed I/O devices with grounded reference potential, occurring interference currents are discharged into functional earth. The connections must be externally connected. Establish a connection between 1M or 2M and functional earth.
  • Page 29 Connecting 4.2 Operation on grounded/non-grounded infeed Overall configuration of ET 200eco PN M12-L The following figure shows a ET 200eco PN M12-L distributed I/O device with electrical overall configuration. ① Main switch ② Short-circuit and overvoltage protection ③ Fuses for cable protection ④...
  • Page 30 Connecting 4.2 Operation on grounded/non-grounded infeed Insulation monitoring In the following situations, you must provide insulation monitoring: • When setting up the ET 200eco PN M12-L distributed I/O devices with non-grounded reference potential • If dangerous system states occur due to error Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...
  • Page 31: Electrical Configuration Of The Et 200Eco Pn M12-L

    Connecting 4.3 Electrical configuration of the ET 200eco PN M12-L Electrical configuration of the ET 200eco PN M12-L Electrical isolation The electrical configuration of the ET 200eco PN M12-L features electrical isolation between: • 1L+: Non-switched supply voltage (electronics/sensor/load supply): Isolated from PROFINET IO and 2L+ (load voltage supply) •...
  • Page 32 Connecting 4.3 Electrical configuration of the ET 200eco PN M12-L Connection of a digital output with a digital input NOTICE Pay attention to the potential groups When a digital output is connected to a digital input, pay attention to the potential groups. Depending on the configuration, 1M and 2M can then be connected, resulting in elimination of the electrical isolation between 1L+ and 2L+.
  • Page 33 Connecting 4.3 Electrical configuration of the ET 200eco PN M12-L Power supply of the configuration Two voltage groups are available for the ET 200eco PN M12-L distributed I/O devices. • 1L+ (supply voltage / non-switched) • 2L+ (load voltage / switched) A renewed voltage supply of 1L+ and 2L+ may be necessary.
  • Page 34: Connecting Et 200Eco Pn M12-L To The Functional Earth

    Connecting 4.4 Connecting ET 200eco PN M12-L to the functional earth Connecting ET 200eco PN M12-L to the functional earth Introduction You must connect the ET 200eco PN M12-L distributed I/O devices to the functional earth. What is functional earth? All ET 200eco PN M12-L I/O devices feature a functional-earth connection.
  • Page 35: Mounting Et 200Eco Pn M12-L On Non-Conductive Surface

    Connecting 4.4 Connecting ET 200eco PN M12-L to the functional earth Mounting Proceed as follows to connect ET 200eco PN M12-L distributed I/O devices to functional earth with a conductive mounting surface: 1. Drill two fastening holes. The dimensions of the I/O device can be found in the section Dimension drawing (Page 80).
  • Page 36 Connecting 4.4 Connecting ET 200eco PN M12-L to the functional earth Required accessories To connect to functional earth on a non-conductive fastening substrate, you need the following accessories: • 2 x 5 mm fixing screws • Cable lug, suitable for 5 mm screws •...
  • Page 37 Connecting 4.4 Connecting ET 200eco PN M12-L to the functional earth The figure below shows how to connect functional earth. Figure 4-4 Connecting the functional earth Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...
  • Page 38: Connecting Cables For Et 200Eco Pn M12-L

    Connecting 4.5 Connecting cables for ET 200eco PN M12-L Note Earthing with non-conductive mounting substrate Make sure there is a low-impedance connection between the I/O device and the functional earth. Reference You will find more information on installing the I/O devices in the section Mounting (Page 18).
  • Page 39 Connecting 4.5 Connecting cables for ET 200eco PN M12-L Derating of the input currents The table below shows the maximum permissible input current of the distributed I/O systems depending on the ambient temperature. Table 4- 2 Deratings of the input currents while maintaining the minimum clearance Ambient temperature Max.
  • Page 40: Wiring

    Connecting 4.6 Wiring Wiring Wiring Connect all cables to the front side of the I/O device: • Supply voltage to the 4-pin M12-L coded round connectors and round sockets • Signal lines to the 5-pin M12-A coded round sockets • PROFINET I/O lines on the 4-pin M12-D coded round sockets Requirement Wire the I/O devices with the supply voltage off.
  • Page 41 Connecting 4.6 Wiring The following figure shows the connection of several I/O devices to the supply voltage and the PROFINET IO as an example. Figure 4-5 Connecting the supply voltage and PROFINET IO Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...
  • Page 42 Connecting 4.6 Wiring The following figure shows the connection of the sensor / actuator M12 connectors. Figure 4-6 Connect sensor/actuator cable Pin assignment of the sockets The pin assignment of the sockets can be found in the manuals of the I/O device in the section on pin assignment.
  • Page 43 Connecting 4.6 Wiring Y- connection The Y-connection allows you to connect two actuators or sensors to the inputs or outputs of the I/O devices. The use of a Y-cable or the Y-connector is particularly recommended when two channels are occupied for each socket of an I/O device. The Y-cable or the Y-connector distributes the two channels to two circular connectors.
  • Page 44: Marking The Et 200Eco Pn M12-L

    Connecting 4.7 Marking the ET 200eco PN M12-L Marking the ET 200eco PN M12-L 4.7.1 Factory markings Introduction For better orientation, the ET 200eco PN M12-L distributed I/O system is identified using various markings which will help you when configuring and connecting the I/O devices. Marking of the interfaces The interfaces of the I/O devices are factory-labeled.
  • Page 45: Optional Markings

    Connecting 4.7 Marking the ET 200eco PN M12-L 4.7.2 Optional markings Introduction In addition to the factory markings, there are also optional possibilities for labeling and/or identifying interfaces and I/O devices on the ET 200eco PN M12-L distributed I/O system. Identification label The identification labels come with each I/O device as strips and can be machine-printed.
  • Page 46: Mounting Identification Labels

    Connecting 4.7 Marking the ET 200eco PN M12-L 4.7.3 Mounting identification labels Introduction This section describes how to mount or remove identification labels. Required tools You need a screwdriver with 3 mm blade width (only to remove identification labels). Mounting procedure To mount an identification label, proceed as follows: 1.
  • Page 47: Configuring

    Configuring the ET 200eco PN M12-L with STEP 7 TIA Portal Information on the configuration can be obtained from the STEP 7 online help and in the SIMATIC PROFINET with STEP 7 (https://support.industry.siemens.com/cs/ww/en/view/49948856) system manual. Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...
  • Page 48: Isochronous Real-Time Communication

    You can find additional information on the topic of isochronous real-time communication in the STEP 7 online help and in the SIMATIC PROFINET with STEP 7 (https://support.industry.siemens.com/cs/ww/en/view/49948856) function manual. Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...
  • Page 49: Isochronous Mode

    Detailed information You can find additional information on the topic of isochronous mode in the STEP 7 online help and in the SIMATIC PROFINET with STEP 7 (https://support.industry.siemens.com/cs/ww/en/view/49948856) function manual. Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...
  • Page 50: Shared Device

    Detailed information You can find additional information on the topic of shared device in the STEP 7 online help and in the SIMATIC PROFINET with STEP 7 (https://support.industry.siemens.com/cs/ww/en/view/49948856) function manual. Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...
  • Page 51: Module-Internal Shared Input / Shared Output (Msi/Mso)

    Detailed information You can find additional information on the topic of Module-internal shared input / shared output (MSI/MSO) in the STEP 7 online help and in the SIMATIC PROFINET with STEP 7 (https://support.industry.siemens.com/cs/ww/en/view/49948856) function manual. System redundancy S2 System redundancy S2 An IO device with S2 system redundancy supports redundant ARs.
  • Page 52: Prioritized Startup

    PROFINET IO system with IRT communication as of FW V1.1.0. Detailed information You can find more information in the SIMATIC PROFINET with STEP 7 (https://support.industry.siemens.com/cs/ww/en/view/49948856) system manual. Device replacement without programming device Requirement A topology must be created in the project.
  • Page 53: Media Redundancy

    (STEP 7 V5.5 and higher). For additional information, refer to the STEP 7 online help and the SIMATIC PROFINET with STEP 7 (https://support.industry.siemens.com/cs/ww/en/view/49948856) manual. Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...
  • Page 54: Commissioning The

    Commissioning the Commissioning ET 200eco PN M12-L on PROFINET IO Introduction The commissioning of your distributed I/O devices depends on the respective plant configuration. The following procedure describes how to commission the ET 200eco PN M12-L on an IO controller. Requirements for commissioning on the PROFINET IO Note Performing tests...
  • Page 55: Startup Of The I/O Device

    2. Switch on the power supply 2L+, if necessary. Reference You can find additional information in the STEP 7 online help and in the manual SIMATIC PROFINET with STEP 7 (https://support.industry.siemens.com/cs/ww/en/view/49948856). Startup of the I/O device 6.2.1 Unconfigured without PROFINET IO...
  • Page 56: Unconfigured On Profinet Io

    Commissioning the 6.2 Startup of the I/O device 6.2.2 Unconfigured on PROFINET IO Startup without parameter assignment on PROFINET IO The following schematic diagram shows the startup of the ET 200eco PN M12-L in factory setting, without PROFINET IO: Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...
  • Page 57: Configured On Profinet Io

    Commissioning the 6.2 Startup of the I/O device 6.2.3 Configured on PROFINET IO Startup configured on PROFINET IO The following schematic diagram shows the startup of the ET 200eco PN M12-L I/O device on PROFINET IO: Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...
  • Page 58: Identification And Maintenance Data

    Commissioning the 6.3 Identification and maintenance data Identification and maintenance data 6.3.1 Reading out and entering I&M data Introduction I&M identification data is information which is stored on the I/O device either as read-only data (I-data) or read/write data (M-data). Identification data (I&M0): Manufacturer information on the I/O device that is read-only and in some cases is also lasered on the I/O device housing, for example, article number, serial number and firmware version.
  • Page 59: Data Record Structure For I&M Data

    Commissioning the 6.3 Identification and maintenance data Procedure for input of maintenance data using STEP 7 The default module name is assigned by STEP 7. You have the option to enter the following data: • Plant designation (I&M1) • Location identifier (I&M1) •...
  • Page 60 Explanation Identification data 0: (data record index AFF0 hex) VendorIDHigh read (1 byte) This is where the name of the manufac- turer is stored (42 = SIEMENS AG). VendorIDLow read (1 byte) Order_ID read (20 bytes) 6ES7141-6BG00-0BB0 Order number of the I/O device (e.g. of...
  • Page 61: Maintenance

    Maintenance Replacing an I/O device Replacing an I/O device Replacing an I/O device is not permitted during ongoing operation. NOTICE Material damage can occur If you connect or disconnect the I/O devices with the power connected, this can lead to undefined states in your system.
  • Page 62 Maintenance 7.1 Replacing an I/O device WARNING Observe the connection sequence of I/O devices If you mix up the ET 200eco PN M12-L I/O devices or lines when connecting them, this can cause personal injury and damage to the machine. We recommend that you clearly label the ET 200eco PN M12-L I/O devices with the device number.
  • Page 63 Maintenance 7.1 Replacing an I/O device Result Topological configuration: 1. The new I/O device automatically receives the device name via the IO controller. Note New or factory setting The I/O device only then obtains the device name automatically: • New I/O device •...
  • Page 64: Firmware Update

    • Online via STEP 7, TIA Portal V16 or higher Reference You can find additional information on the procedure in the FAQs on the Internet (http://www.siemens.com/automation/service&support) and in the online help for STEP 7. Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...
  • Page 65: Resetting The I/O Device To Factory Settings

    Maintenance 7.3 Resetting the I/O device to factory settings Resetting the I/O device to factory settings Introduction When you "Reset to factory settings", the I/O device is reset to the "delivery state". All information that was saved internally on the I/O device is deleted. Result after resetting to factory settings The following table shows an overview of the contents of the saved items after resetting to factory settings.
  • Page 66 Maintenance 7.3 Resetting the I/O device to factory settings Procedure with STEP 7 (TIA Portal) Connect the PG/PC to the PROFINET IO interface of the ET 200eco PN M12-L distributed I/O system. Make sure that there is an online connection to the I/O device which is to be reset to factory settings.
  • Page 67: Maintenance And Repair

    Maintenance 7.4 Maintenance and repair Maintenance and repair The components of the SIMATIC ET 200eco PN M12-L system are maintenance-free. Note Repairs to an ET 200eco PN M12-L I/O device may only be carried out by the manufacturer. Cleaning the I/O device When wired, ET 200eco PN M12-L I/O devices comply with degree of protection IP65/IP67 and do not require any cleaning.
  • Page 68: Technical Specifications

    • 2011/65/EU "Restriction of the use of certain hazardous substances in electrical and electronic equipment" (RoHS Directive) The EC Declarations of Conformity are available for the responsible authorities and are kept at the following address: Siemens AG Digital Factory Factory Automation DI FA TI COS TT P.O.
  • Page 69 Technical specifications 8.1 Standards and authorizations RCM Declaration of conformity for Australia/New Zealand The ET 200eco PN M12-L distributed I/O system meets the requirements of the standard EN 61000-6-4:2007+A11:2011 Korea Certificate KCC-REM-S49-ET200 Note that this device corresponds to limit class A with regard to the emission of radio interference.
  • Page 70 Using the ET 200eco PN M12-L distributed I/O system in residential areas can affect radio or television reception. Reference The certificates for the markings and approvals can be found on the Internet under Service&Support (http://www.siemens.com/automation/service&support). Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...
  • Page 71: Electromagnetic Compatibility

    Technical specifications 8.2 Electromagnetic compatibility Electromagnetic compatibility Definition Electromagnetic compatibility is the ability of an electrical apparatus to function in a satisfactory manner in its electromagnetic environment without affecting this environment. An ET 200eco PN M12-L distributed I/O device fulfills the requirements of the EMC law of the European Union.
  • Page 72 Technical specifications 8.2 Electromagnetic compatibility Table 8- 3 RF coupling (signal and supply cables) RF coupling according to IEC 61000-4-6. Corresponds with degree of severity 0.15 ... 80 MHz 10 V unmodulated 80% AM (1 kHz) 150 Ω source impedance Emission of radio frequency interference The following table shows the interference emission of electromagnetic fields according to 55016: limit class A, group 1.
  • Page 73: Transport And Storage Conditions

    • The conditions of use exceed the requirements pursuant to IEC 61131-2 – Class OTH2 You can find the values for the operating conditions in the technical specifications of the equipment manuals or on the Internet (https://support.industry.siemens.com/cs/de/en/view/109742718). Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...
  • Page 74 Technical specifications 8.4 Mechanical and climatic ambient conditions Tests of mechanical ambient conditions The following table shows the type and scope of the tests on mechanical ambient conditions. Table 8- 7 Tests of mechanical ambient conditions Condition tested Test standard Values Sinusoidal vibra- Vibration test accord-...
  • Page 75 Technical specifications 8.4 Mechanical and climatic ambient conditions Use above 2000 m is possible. The following constraints apply to the maximum specified ambient temperature: Derating factor of installation elevation and ambient temperature Table 8- 9 Installation elevation Derating factor for ambient temperature -1000 ...
  • Page 76: Details On Insulation, Protection Class, Degree Of Protection And Rated Voltage

    Technical specifications 8.5 Details on insulation, protection class, degree of protection and rated voltage Details on insulation, protection class, degree of protection and rated voltage Insulation The insulation is designed in compliance with the requirements of IEC 61010-2-201. Note In the case of I/O devices with 24 V DC (SELV/PELV) supply voltage, galvanic isolations are tested with 707 V DC (type test).
  • Page 77: Safety Related Icons For Et 200Eco Pn M12-L

    Technical specifications 8.6 Safety related icons for ET 200eco PN M12-L Rated voltage for operation The following table shows the nominal voltage and the corresponding tolerance with which the ET 200eco PN M12-L distributed I/O system operates. Table 8- 10 Rated voltage for operation Rated voltage (SELV/PELV) Tolerance range...
  • Page 78: Safety-Related Shutdown

    Safety-related shutdown Introduction The diagram below illustrates the fail-safe shutdown of ET 200eco PN M12-L standard modules. In the configuration shown in the diagram below (e.g. with the safety shutdown device 3SK1), all digital outputs that are connected to the 2L+ and 2M supply (24 V switched) of the ET 200eco PN M12-L standard modules are switched to the safe OFF state.
  • Page 79 Safety-related shutdown Block diagram Figure A-1 Higher-level safety circuit of the outputs WARNING Note potential groups for safety-related shutdown When a digital output is connected to a digital input, pay attention to the potential groups. Depending on the configuration, 1M and 2M can then be connected, which leads to elimination of the electrical isolation between 1L+ and 2L+.
  • Page 80 In this FAQ, you can find the SIMATIC standard modules that are suitable for safety-related shutdown. Request German Technical Inspectorate report (Report no. SN96753T) You can request copies of the German Technical Inspectorate report at the following address: SIEMENS AG Digital Industries DI FA TI COS TT P.O. Box 1963...
  • Page 81: Dimension Drawings

    Dimension drawings Dimension drawing This module dimension is available for the ET 200eco PN M12-L distributed I/O system. Figure B-1 Dimension drawing Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...
  • Page 82: Accessories/Spare Parts

    Accessories/spare parts Accessories/spare parts Accessories for the ET 200eco PN M12-L distributed I/O system Table C- 1 Accessories for power supply Designation Length Article number Cable is pre-assembled CONNECTING CABLE M12, L-CODED 0.5 m 6XV1801-6DE50 Power connecting cable M12-180/M12-180 for power 1.0 m 6XV1801-6DH10 supply of ET 200...
  • Page 83 Accessories/spare parts C.1 Accessories/spare parts Table C- 2 Non-preassembled connector PROFINET M12 Designation Article number Non-preassembled connectors for X1 P1R PN (LAN) and X1 P2R PN (LAN) socket PROFINET M12 plug connector D-coded with Fast- 1 unit/ 6GK1901-0DB10-6AA0 Connect connection system, 180° pack 8 units/ 6GK1901-0DB10-6AA8...
  • Page 84 Accessories/spare parts C.1 Accessories/spare parts Table C- 4 Pre-assembled cable PROFINET M12 Designation Article number Pre-assembled cable for X1 P1R PN (LAN) and X1 P2R PN (LAN) PROFINET M12 connecting cable, trailing cable, pre- 0.3 m 6XV1870-8AE30 assembled on both ends with M12 connectors 180° 0.5 m 6XV1870-8AE50 (pin)
  • Page 85 6GK1901-1GA00 Online catalog Other article numbers for the ET 200eco PN M12-L distributed I/O system can be found on the Internet (http://www.siemens.com/automation/service&support) in the online catalog and the online order system. Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...
  • Page 86: Ul-Approved Cables

    UL-approved cables from PHOENIX CONTACT In combination with the cables listed for the power supply of the manufacturer PHOENIX CONTACT, the SIMATIC ET 200eco PN M12-L distributed I/O devices meet the UL approval. Table C- 7 Accessories for power supply...
  • Page 87 C.2 UL-approved cables UL-approved cables from Siemens In combination with the cables listed for the connection of DI/DQ of the manufacturer Siemens, the SIMATIC ET 200eco PN M12-L distributed I/O devices meet the UL approval. Table C- 8 Accessories for DI/DQ connection...
  • Page 88: Glossary

    Glossary A common transfer route connecting all nodes and having two defined ends. Configuration Systematic arrangement of the individual I/O devices (configuration). Connection plug Physical connection between device and cable. Derating Derating allows devices to be used even in harsh operating conditions by selectively restricting the output capacity.
  • Page 89 Glossary Ground A part of the ground, which is considered conductive and whose electrical potential is usually assumed to be zero, is outside the zero point of influence of a grounding arrangement. All electrically conductive, interconnected, inactive parts of a piece of equipment that cannot accept any dangerous contact voltage, even in the event of a fault.
  • Page 90 Glossary PROFINET IO device Distributed field device that can be assigned to one or more IO controllers (for example distributed I/O system, valve terminals, frequency converters, switches). PROFINET IO Communication concept for the realization of modular, distributed applications in the framework of PROFINET.
  • Page 91: Index

    Index Electrostatic discharge, 70 EMC, 70 EMERGENCY-STOP device, 23 Emission of radio frequency interference, 71 24 V DC supply, 24 ET 200eco PN M12-L Commissioning, 54 ET 200eco PN M12-L distributed I/O device Area of application, 13 Accessories, 81 ET 200eco PN M12-L distributed I/O system Ambient conditions Components, 15 Climatic, 73...
  • Page 92 Screws, 19, 21 SELV, 26, 27 Shared device, 49 Shared Input, 50 Shared output, 50 Shock, 73 SIMATIC ET 200eco PN M12-L, 12 Sinusoidal disturbance variables, 70 Sockets, 42 Distributed I/O system ET 200eco PN M12-L System Manual, 06/2021, A5E48753295-AC...

Table of Contents