I/O device analog input/analog output
10.1 I/O device analog input
Technical data
Electrical isolation
"No temperature compensation" is always run when using the measuring type ±80 mV regardless of
1
the configured temperature compensation.
With 3-wire resistance measurement (and thermal resistor) the measuring resistances and the line
2
resistances are updated in alternating cycles. Rapid changes in the measuring resistance therefore
impair the accuracy.
For thermocouples, the information refers to the temperature range from -100 °C to nominal value
3
Note
The accuracy information is valid for static thermal states and changes in ambient
temperature < 1 K/h.
The I/O device achieves the highest accuracy with the 4-wire connection system (see
technical specifications above).
Although the 3-wire connection system compensates for the missing wire, the accuracy is
impaired. With the 2-wire connection system, the line resistances considerably impair the
accuracy.
In the last two cases this impairment is not determinable.
Note
With the 3-wire connection system, the compensation of the missing cable is only ensured if
all three cores in the cable have the same length and cross-section.
See also
Response times for analog input device and output device (Page 258)
162
Between 1L+ and 2L+
Between 1L+, channels and all other circuit
elements
Between channels
Between Ethernet and all other circuit ele-
ments
Yes
No
No
Yes
Operating Instructions, 08/2016, A5E01250250-AJ
ET 200eco PN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents