3 Electrical Installation
 Wiring Specification
Main Circuit
Use the line filters listed up in the table below when wiring the main circuit. Make sure not
to exceed the given tightening torque values.
Model
EMC Filter
CIMR-LC
[Schaffner]
4V0007
FS23639-10-07
4V0009
FS23639-15-07
4V0015
FS23639-30-07
4V0018
4V0024
FS23639-50-07
4V0031
Input Fuse Selection
Branch circuit protection shall be provided by any of the following:
• Non-time delay Class J, T, or CC fuses sized at 300% of the drive input rating
• Time delay Class J, T, or CC fuses sized at 175% of the drive input rating
• Time-delay Class RK5 fuses sized at 225% of the drive input rating
Model
(Manufacturer: Ferraz)
CIMR-LC
600 VAC, 200 kAIR
4V0007
4V0009
4V0015
4V0018
4V0024
4V0031
Control Circuit
The control terminal board is equipped with screwless terminals. Always use wires within
the specification listed below. For safe wiring it is recommended to use solid wires or flexi-
ble wires with ferrules. The stripping length respectively ferrule length should be 8 mm.
EN 12
AC Reactors
B 0903084
B 0903085
B 0903086
B 0903087
Main Fuse
Fuse Ampere
TRS20R
TRS30R
A6T50
60
A6T60
A6T70
70
80
A6T80
Wire Type
Solid
Flexible
Flexible with ferrule
YASKAWA Europe TOEP C710606 91B AC Drive L1000H - Quick Start Guide
Recom.
Motor cable
U/T1,V/T2,W/T3, - ,
(mm²)
2.5
2.5
6
10
10
16
(Manufacturer:
Rating (A)
500 VAC, 200 kAIR
20
30
50
Wire size (mm
0.2 to 1.5
0.2 to 1.0
0.25 to 0.5
Main Circuit Terminal Sizes
R/L1,S/L2,T/L3,
B1, B2
+1, +2
M4
M4
M4
M4
M5
M5
Fuse Type
Fuse Ampere
Bussmann)
FWH-90B
FWH-90B
FWH-80B
FWH-100B
FWH-125B
FWH-200B
2
)
M4
M4
M4
M4
M4
M5
M4
M5
M5
M5
M5
M6
Rating (A)
90
90
80
100
125
200