Download Print this page

YASKAWA L1000H Quick Start Manual page 15

400 v class, three-phase input: 3.0 to 15.0 kw. type: cimr-lc4v0007b-0011 cimr-lc4v0009b-0011 cimr-lc4v0015f-0011 cimr-lc4v0018f-0011 cimr-lc4v0024f-0011 cimr-lc4v0031f-0011
Hide thumbs Also See for L1000H:

Advertisement

• Separate wiring for control circuit terminals MA, MB, MC (contact output) from wiring
to other control circuit terminals.
• For external control power supply use a UL Listed Class 2 power supply.
• Use twisted-pair or shielded twisted-pair cables for control circuits to prevent operating
faults.
• Ground the cable shields with the maximum contact area of the shield and ground.
• Cable shields should be grounded on both cable ends.
• If flexible wires with ferrules are connected they might fit tightly into the terminals. To
disconnect them, grasp the wire end with a pair of pliers, release the terminal using a
straight-edge screw driver, turn the wire for about 45 and pull it gently out of the termi-
nal. For details, refer to the Technical Manual. Use this procedure for removing the wire
link between HC, H1 and H2 when the Safe Disable function is utilized.
Main Circuit Terminals
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
B1, B2
+1, +2
+1, –
(2 terminals)
Control Circuit Terminals
The figure below shows the control circuit terminal arrangement. The drive is equipped with
screwless terminals.
P1 P2 PC A1 A2 +V AC AM AC MP
S1 S2 S3 S4 S5 S6 SC HC H1 H2 RP
YASKAWA Europe TOEP C710606 91B AC Drive L1000H - Quick Start Guide
Type
Main circuit power
Connects line power to the drive.
supply input
Drives with single-phase 200 V input power have no T/L3 terminal.
Drive output
Connects to the motor.
Braking resistor
For connecting a braking resistor or the braking resistor unit option.
DC reactor connec-
Linked at shipment. Remove the link to install a DC choke.
tion
DC power supply
For connecting a DC power supply.
input
Ground with 10  or less
Ground Terminal
S1
S2
R+ R- S+ S- IG
S3
MA MB MC
3 Electrical Installation
Function
Use a straght-edge screwdriver
with a blade width of max 2.5 mm
and a thickness of max 0.6 mm to
release the terminals
EN 15

Hide quick links:

Advertisement

loading