5 Start Up
Teaching Mode
Basic Calculations
Empty Car Teach Run
Save Teach Results
Step 1: Basic Calculations - P4-01 = 1
Perform as following to provide the basic parameters:
• Enter the programming menu.
• Enter the pump parameter data as received with the valve package or calculated on the
web page http://www.blain.de/calc into P1- parameters.
• Set P4-01 = 1.
If teaching finished successfully, the display will first show "END" directly followed by "0".
Parameter P4-01 will be reset to 0 automatically.
In case that the drive shows oPE12 alarm (ALM LED flashing), check and correct the P1
settings.
The following table shows the data to be input:
EN 22
Parameter
P4-01 = 1
P4-01 = 2
P4-01 = 3
START
Enter P1-
parameters.
Set P4-01 =
1.
oPE12
alarm shown?
NO
Finish
YASKAWA Europe TOEP C710606 91B AC Drive L1000H - Quick Start Guide
Based on pump, oil and elevator data, the drive sets e. g. fre-
quency references.
Determines remaining operation data during an empty car teach
run.
Save the results of empty car teach run.
YES
Description