5 Start Up
 Drive Sequence and Run Command for Down Travel
Travel Procedure
The down travel sequence is shown in the figure below. The Down Travel Run command
and the Down Speed Command must be set given according to this sequence.
Capturing Torque
Leveling
Down Travel Run
Down Speed
Down Valve Control
Time
Leveling Control
In case of wrong setup (e. g. P1 parameter incorrectly entered), the pump might not generate
enough flow to move the car after deceleration from the selected speed to leveling speed.
To allow recovery in such a case, the drive decreases the speed automatically in steps down
to zero value in case the Down Travel RUN command is still on. Refer to the figure below.
Leveling
Frequency Reference
Soft Starter Output
Down Travel
Run Command
Time
EN 30
P2-03 = 0 (Energy Saving)
P2-04
P2-19
P2-12
P2-13
(Down Leveling
Control Wait Time)
P2-14
YASKAWA Europe TOEP C710606 91B AC Drive L1000H - Quick Start Guide
P2-03 > 0 (Normal)
P2-06
Stop
P6-07