Download Print this page

YASKAWA L1000H Quick Start Manual page 33

400 v class, three-phase input: 3.0 to 15.0 kw. type: cimr-lc4v0007b-0011 cimr-lc4v0009b-0011 cimr-lc4v0015f-0011 cimr-lc4v0018f-0011 cimr-lc4v0024f-0011 cimr-lc4v0031f-0011
Hide thumbs Also See for L1000H:

Advertisement

Par.
Name
Duty Mode and Carrier Frequency
1:2.0 kHz
2:5.0 kHz
3:8.0 kHz
Carrier
4:10.0 kHz
C6-02
Frequency
5:12.5 kHz
Selection
6:15.0 kHz
7 to A: Swing PWM1 to 4
F: User defined
V/f Pattern
Input
E1-01
Voltage
Input Voltage
Setting
Max. Out-
For a linear V/f characteristics, set
E1-04
put Freq.
the same values for E1-07 and E1-
09. In this case, the setting for E1-
Max. Out-
E1-05
08 will be disregarded.
put Voltage
Ensure that the four frequencies are
set according to these rules or
Base
E1-06
OPE10 fault will occur:
Frequency
Middle Out-
E1-04  E1-06  E1-07  E1-09
E1-07
put Freq.
Output voltage
(E1-05)
Mid. Out-
E1-08
(E1-13)
put Voltage
Min. Out-
E1-09
put Freq.
(E1-08)
Min. Out-
E1-10
put Voltage
(E1-10)
Base
E1-13
Voltage
Motor Data
Motor
Automatically set during Auto-Tun-
E2-01
Rated
ing.
Current
Motor rated slip in hertz (Hz).
Motor
E2-02
Automatically set by Rotational
Rated Slip
Auto-Tuning.
Motor
Magnetizing current in Ampere.
E2-03
No-Load
Automatically set by Rotational
Current
Auto-Tuning.
Number of motor poles.
E2-04 Motor Poles
Automatically set by Auto-Tuning.
YASKAWA Europe TOEP C710606 91B AC Drive L1000H - Quick Start Guide
Description
(E1-09)
(E1-07)
(E1-06)
(E1-04)
Output frequency
Par.
Name
Motor Line-
Sets the phase-to-phase motor
E2-05
to-Line
resistance in ohms.
Resistance
Automatically set by Auto-Tuning.
Sets the voltage drop due to motor
Motor
leakage inductance as a percentage
E2-06
Leakage
of motor rated voltage.
Inductance
Automatically set by Auto-Tuning.
Digital Input Settings
H1-01
DI S1 to S6
Selects the function of terminals S1
to
Function
to S6.
H1-06
Selection
Major functions are listed at the end of the table.
Digital Output Settings
DO MA/
Set the function for the relay output
H2-01
MB Func-
MA-MB-MC.
tion
DO P1
Sets the function for the photocou-
H2-02
Function
pler output P1.
DO P2
Sets the function for the photocou-
H2-03
Function
pler output P2.
Major functions are listed at the end of the table.
Analog Input Setting
A1 Signal
0:0 to +10 V (neg. input is zeroed)
H3-01
Level Sel.
1:0 to +10 V (bipolar input)
A1
H3-02
Function
Assign a function to terminal A1.
Sel.
Sets the input value in % at 10 V
H3-03 A1 Gain
analog input.
Sets the input value in % at 0 V
H3-04 A1 Bias
analog input.
0:0 to +10 V (neg. input is zeroed)
A2 Signal
1:0 to +10 V (bipolar input)
H3-09
Level
2:4 to 20 mA (9 bit input)
Selection
3:0 to 20 mA
A2
H3-10
Function
Assign a function to terminal A2.
Sel.
Sets the input value in % at
H3-11 A2 Gain
10 V/20 mA analog input.
Sets the input value in % at
H3-12 A2 Bias
0 V/0 mA/4 mA analog input.
6 Parameter Table
Description
EN 33

Hide quick links:

Advertisement