YASKAWA L1000H Quick Start Manual page 16

400 v class, three-phase input: 3.0 to 15.0 kw. type: cimr-lc4v0007b-0011 cimr-lc4v0009b-0011 cimr-lc4v0015f-0011 cimr-lc4v0018f-0011 cimr-lc4v0024f-0011 cimr-lc4v0031f-0011
Hide thumbs Also See for L1000H:

Advertisement

3 Electrical Installation
There are three DIP switches, S1 to S3, located on the terminal board
SW1
Switches analog input A2 between voltage and current input
SW2
Enables or disables the internal RS422/485 comm. port terminal resistance.
Used to select sourcing (PNP)/sinking (NPN, default) mode for the digital inputs (PNP requires
SW3
external 24 VDC power supply)
Control Circuit Terminal Functions
Type
No.
S1
Multi-
to
Multi-function digital input 1 to 6
Function
S6
Digital
Inputs
SC
Multi-function input common
RP
Not used
Multi-
+V
Analog input power supply
Function
Analog/
A1
Multi-function analog input 1
Pulse
A2
Multi-function analog input 2
Inputs
AC
Analog input common
HC
Safe Disable Input common
Safe
H1
Safe Disable Input 1
Disable
Inputs
H2
Safe Disable Input 2
Multi-
MA N.O. (fault)
Function
MB
N.C. output (fault)
Relay
MC
Digital output common
Output
Multi-
P1
Photocoupler output 1
Function
P2
Photocoupler output 2
PHC
PC
Photocoupler output common
Output
MP
Pulse train output
Monitor
AM Analog monitor output
Output
AC
Monitor common
R+
Communications input (+)
MEMO-
R–
Communications input (–)
BUS/
Commu-
S+
Communications output (+)
nication
S-
Communications output (–)
NOTICE! The terminals HC, H1, H2 are used for the Safe Disable function which cuts the
output voltage in less than 1 ms if at least one of the inputs H1 or H2 is opened. It is
designed in accordance with the EN954-1, safety category 3 and EN61508, SIL2. It
and can be utilized to perform a safe stop as defined by the EN60204-1, stop
category 0. Do not remove the wire link between HC, H1, or H2 unless the Safe
Disable function is used. Refer to the Technical Manual when using this function.
NOTICE! The wiring length to the terminals HC, H1 and H2 should not exceed 30 m.
EN 16
Terminal Name (Signal)
YASKAWA Europe TOEP C710606 91B AC Drive L1000H - Quick Start Guide
Function (Signal Level), Default Setting
Photocoupler inputs, 24 VDC, 8 mA
Note: Drive preset to sinking mode (NPN). When using
source mode, set DIP switch S3 to "SOURCE" and use an
external 24 VDC (±10%) power supply.
Sequence common
+10.5 V (max allowable current 20 mA)
0 to +10 VDC (20 k) resolution 1/1000
0/4 to 20 mA (250 ) resolution: 1/500 (A2 only)
0 V
+24 V (max 10 mA allowed)
One or both open: Drive output disabled (time from input
open to drive output switch off is less than 1 ms)
Both Closed: Normal operation
Digital relay output
30 VDC, 10 mA to 1 A
250 Vac, 10 mA to 1 A
Digital photocoupler output
48 VDC, 2 to 50 mA
32 kHz (max)
0 to 10 VDC (2 mA or less), Resolution: 1/1000 (10 bit)
0 V
MEMOBUS/Modbus communication.:
RS-485 or RS-422, 115.2 kbps (max)