3 Electrical Installation
• If using a ground fault circuit breaker, make sure that it can detect both DC and high fre-
quency current.
• When frequently switching on/off power supply (e. g. for energy saving reasons) make
sure the power is not cycled more than 54 times per day.
• Use a DC reactor or AC reactor on the input side of the drive:
• To suppress harmonic current.
• To improve the power factor on the power supply side.
• When using an advancing capacitor switch.
• With a large capacity power supply transistor (over 600 kVA).
Wiring the Main Circuit Output
Consider the following precautions for the output circuit wiring.
• Do not connect any other load than a 3 phase motor to the drives output.
• Never connect a power source to the drives output.
• Never short or ground the output terminals.
• Do not use phase correction capacitors.
• If using a contactor between the drive and motor, it should never be operated when the
drive is outputting a voltage. Operating while there is voltage output can cause large peak
currents, thus tripping the over current detection or damage the drive.
Ground Connection
Take the following precautions when grounding the drive:
• The drive must always be connected to ground in accordance to the general technical stan-
dards and local regulations.
As the leakage current produced by the drive exceeds 3.5 mA, according to IEC 61800-5-
1, at least one of the conditions below must be satisfied:
• The cross-section of the protective earthing conductor must be at least 10 mm
or 16 mm
(Al).
2
• The power supply must be disconnected automatically in case of discontinuity of the
protective earthing conductor.
• Keep ground wires as short as possible.
• Always make sure the ground impedance is conformed to the requirements of local safety
and installation regulations.
• Never share the ground wire with other devices such as welding machines, etc.
• Do not loop the ground wire when using more than one drive.
Control Circuit Wiring Precautions
Consider the following precautions for wiring the control circuits.
• Separate control circuit wiring from main circuit wiring and other high-power lines.
EN 14