8 Instructions for UL and cUL
8
Instructions for UL and cUL
UL Standards Compliance
This drive is tested in accordance with UL standard UL508C, File No. E131457 and com-
plies with UL requirements. To ensure continued compliance when using this drive in com-
bination with other equipment, meet the following conditions:
Installation Area
Do not install the drive to an area greater than pollution severity 2 (UL standard).
Main Circuit Terminal Wiring
YASKAWA recommends using UL-listed copper wires (rated at 75C) and closed-loop con-
nectors or CSA-certified ring connectors sized for the selected wire gauge to maintain
proper clearances when wiring the drive. Use the correct crimp tool to install connectors per
manufacturer recommendation. The following table lists a suitable closed-loop connector
manufactured by JST Corporation.
Closed-Loop Crimp Terminal Size (JIS C 2805) (same for 200 V and 400 V)
Wire Gauge
2
mm
(AWG)
0.75
(18)
1.25
(16)
2
(14)
EN 46
Terminal Screws
M3.5
M4
M3.5
M4
M3.5
M4
M5
M6
YASKAWA Europe TOEP C710606 91B AC Drive L1000H - Quick Start Guide
Crimp Terminal
Model Number
R1.25-3.5
R1.25-4
R1.25-3.5
R1.25-4
R2-3.5
R2-4
R2-5
R2-6
Tightening Torque
Nm
(lbin.)
0.8 to 1.0
(7.1 to 8.9)
1.2 to 1.5
(10.6 to 13.3)
0.8 to 1.0
(7.1 to 8.9)
1.2 to 1.5
(10.6 to 13.3)
0.8 to 1.0
(7.1 to 8.9)
1.2 to 1.5
(10.6 to 13.3)
2.0 to 2.5
(17.7 to 22.1)
4.0 to 5.0
(35.4 to 44.3)