1 EMR‑3MP0 Motor Protection Relay
1.3 Modules, Settings, Signals and Values
1.3.5

Device Planning

"Device Planning" means to change the functional range to a degree that suits the
protection task to be fulfilled (i. e.: the device deactivates all functions that are not
needed, and shows only the active ones).
There is a top-level menu item [Device Planning] that is dedicated to this; it collects a
setting parameter for each function which can be set to "-" or to "Use". (In some cases
there are additional setting options, for example with devices featuring direction
determination).
If the user, for example, activates the voltage protection function, all menu branches
related to this function appear in the menu tree. All corresponding events, signals, etc.,
are activated as well.
It MUST be taken into account that Device Planning changes the functionality of the
device.
If, for example, the user cancels the directional feature of the overcurrent protections, the
device will no longer trip in a directional way but merely in a non-directional way. If the
user deactivates a protection function, the device will no longer trip according to the
criteria related to this protection function.
The manufacturer does not accept liability for any personal or material damage as a
result of incorrect planning.
Contact your Eaton Customer Service representative for more information.
Beware of the inadvertent deactivating of protective functions/modules, because all the
settings of a deativated module get lost (i. e. are set back to their respective default
values)!
This means: If the user is activating any of these modules again at some later time, all
parameters of the re-activated modules need to be reconfigured.
40
WARNING!
WARNING!
www.eaton.com
EMR-3MP0