Wiring Example

This example shows wiring for conforming to undervoltage reference.
3-phase power
200 to 240 V
50/60 Hz
Thermal relay trip contact
for Braking Resistor Unit
Thermal relay trip contact
for motor cooling fan
Multi-function
contact inputs
External
frequency
references
* 1. The main circuit is separated from the terminal cover for safety reasons.
* 2. The contact output circuit is separated from the main circuit and the control circuit by reinforced insulation.
It can be connected to extra-low voltage circuits or circuits that are 250 VAC 1 A, 30 VDC 1 A or less.
* 3. The control circuit is an extra-low voltage circuit and separated from the main circuit and the contact output circuit by reinforced insulation. Always
connect it to extra-low voltage circuits.
-14
10
Noise
filter
Forward Run/Stop
Reverse Run/Stop
Thermal switch contact
for Braking Unit
External fault
Fault reset
Multi-step speed reference 1
(Main speed switching)
Fault contact
Multi-step speed
reference 2
Jog frequency
selection
External
Factory
baseblock command
settings
Pulse train input
Frequency setting
adjustment
Frequency
setter
MEMOBUS
communications
RS-485/422
Thermal switch
contact
Braking Unit
(optional)
Level
detector
Inverter
CIMR-F7A2022
(optional)
CN5 (NPN setting)
Shield wire
connection
terminal
Master speed
pulse train
0 to 32 kHz (3 kΩ)
High level: 3.5 to 13.2 V input
Frequency setting power
+15 V, 20 mA
Master speed reference
0 to 10 V (20 kΩ)
Master speed reference
4 to 20 mA (250 Ω)
[0 to 10 V (20 k Ω ) input]
Multi-function anlog input
0 to 10 V (20 kΩ)
Factory setting:
Not used
Terminating
resistance
Fig 10.6
Thermal relay
trip contact
Motor
Braking Resistor Unit
(optional)
Cooling fan
Shielded twisted-pair
wires
Pulse monitor output
Pulse A
30 mA max.
Pulse B
Wiring distance:
d
30 m max.
Pulse train output
0 to 32 kHz (2.2 k Ω)
Default: Output
frequency
Ammeter adjustment
Multi-function analog output 2
-10 to 10 V 2 mA
Default: Output current
0 to +10 V
Ammeter adjustment
Multi-function analog output 1
-10 to 10 V 2 mA
Default: Output frequency
0 to +10 V
Error contact output
250 VAC, 10 mA min. 1 A max.
30 VDC, 10 mA min. 1 A max.
Multi-function contact output
250 VAC, 10 mA min. 1 A max.
30 VDC, 10 mA min. 1 A max.
Default: Running
signal
Open collector 1
Default: Zero-
speed
Multi-function
open-collector outputs
48 VDC 50 mA max.
Open collector 2
Default: Frequency
agree signal