YASKAWA CIMR-F7A Instruction Manual page 56

Varispeed f7 general purpose inverter
Hide thumbs Also See for CIMR-F7A:
Table of Contents

Advertisement

Connecting the Braking Resistor (ERF)
A Braking Resistor that mounts to the Inverter can be used with 200 V and 400 V Class Inverters with outputs
from 0.4 to 3.7 kW.
Connect the braking resistor as shown in Fig 2.13.
L8-01 (Protect selection for internal DB resistor)
L3-04 (Stall prevention selection during deceleration)
(Select either one of them.)
IMPORTANT
Connecting the Braking Resistor Unit (LKEB) and Braking Unit (CDBR)
Use the following settings if using a Braking Resistor Unit and Braking Unit.
A Braking Resistor that mounts to the Inverter can also be used with Inverters with outputs from 0.4 to 3.7
kW.
L8-01 (Protect selection for internal DB resistor)
L3-04 (Stall prevention selection during deceleration)
(Select either one of them.)
L8-01 is used when a braking resistor without thermal overload relay trip contacts (ERF type mounted to
Inverter) is connected.
The Braking Resistor Unit cannot be used and the deceleration time cannot be shortened by the Inverter if L3-
04 is set to 1 (i.e., if stall prevention is enabled for deceleration).
-20
2
Inverter
Fig 2.13 Connecting the Braking Resistor
The braking resistor connection terminals are B1 and B2. Do not connect to any other terminals. Connecting
to any terminals other than B1 or B2 can cause the resistor to overheat, resulting in damage to the equip-
ment.
Table 2.7
1 (Enables overheat protection)
0 (Disables stall prevention function)
3 (Enables stall prevention function with braking resistor)
Braking resistor
Table 2.8
0 (Disables overheat protection)
0 (Disables stall prevention function)
3 (Enables stall prevention function with braking resistor)

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents