Accelerating And Decelerating Heavy Loads (Dwell Function) - YASKAWA CIMR-F7A Instruction Manual

Varispeed f7 general purpose inverter
Hide thumbs Also See for CIMR-F7A:
Table of Contents

Advertisement

Accelerating and Decelerating Heavy Loads (Dwell Function)

The dwell function stores the output frequency when starting or stopping heavy loads. By temporarily storing
the output frequency, you can prevent the motor from stalling. When using the dwell function, you must select
a deceleration stop. Set b1-03 (Stopping Method Selection) to 0.
Related Parameters
Con-
Name
stant
Number
Dwell fre-
b6-01
quency at
start
Run Command
Output frequency
Dwell time
b6-02
at start
Dwell fre-
The dwell function is used to output
b6-03
quency at
frequency temporarily when driving a
stop
motor with a heavy load.
Dwell time
b6-04
at stop
* 1. When C6-01=0, the upper limit is 150.0.
* 2. When C6-01=1, the upper limit is 400.0.
Setting
Description
Range
0.0 to
400.0
1
*
0.0 to
300.0
ON
2
OFF
*
0.0 to
10.0
0.0 to
b6-01
b6-03
Time
400.0
b6-04
b6-02
1
*
0.0 to
300.0
2
*
0.0 to
10.0
Acceleration and Deceleration Characteristics
Control Methods
Change
Open
Factory
during
V/f
Loop
Setting
Opera-
V/f
with
Vec-
tion
PG
tor
0.0 Hz
No
A
A
A
0.0 s
No
A
A
A
0.0 Hz
No
A
A
A
0.0 s
No
A
A
A
MEMO
BUS
Flux
Regis-
Vec-
ter
tor
A
1B6H
A
1B7H
A
1B8H
A
1B9H
29
6-