Detecting Motor Torque

If an excessive load is placed on the machinery (overtorque) or the load is suddenly lightened (undertorque),
you can output an alarm signal to multi-function output terminal M1-M2, P1-PC, or P2-PC.
To use the overtorque/undertorque detection function, set B, 17, 18, 19 (overtorque/undertorque detection NO/
NC) in one of the following constants: H2-01 to H2-03 (multi-function output terminals M1-M2, P1-PC, and
P2-PC function selection).
The overtorque/undertorque detection level is the current level (Inverter rated output current 100%) in V/f
control, and the motor torque (motor rated torque 100%) in vector control.
Related Constants
Con-
stant
Number
Torque detec-
L6-01
tion selection
1
Torque detec-
L6-02
tion level 1
-56
6
Name
Description
0: Overtorque/undertorque
detection disabled.
1: Overtorque detection only
with speed agreement;
operation continues after
overtorque (warning).
2: Overtorque detected
continuously during
operation; operation
continues after overtorque
(warning).
3: Overtorque detection only
with speed agreement;
output stopped upon
detection (protected
operation).
4: Overtorque detected
continuously during
operation; output stopped
upon detection (protected
operation).
5: Undertorque detection only
with speed agreement;
operation continues after
overtorque (warning).
6: Undertorque detected
continuously during
operation; operation
continues after overtorque
(warning).
7: Undertorque detection only
with speed agreement;
output stopped upon
detection (protected
operation).
8: Undertorque detected
continuously during
operation; output stopped
upon detection (protected
operation).
Open loop vector control: Motor
rated torque is set as 100%.
V/f control: Inverter rated cur-
rent is set as 100%.
Control Methods
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0 to 8
0
No
A
0 to 300
150%
No
A
MEMO
Open
BUS
V/f
Flux
Loop
Regis-
with
Vec-
Vec-
ter
PG
tor
tor
A
A
A
4A1H
A
A
A
4A2H