Wiring Terminal Blocks - YASKAWA CIMR-F7A Instruction Manual

Varispeed f7 general purpose inverter
Hide thumbs Also See for CIMR-F7A:
Table of Contents

Advertisement

Wiring Terminal Blocks

Use no more than 100 meters of wiring for PG (encoder) signal lines, and keep them separate from power
lines.
Use shielded, twisted-pair wires for pulse inputs and pulse output monitor wires, and connect the shield to the
shield connection terminal.
Wire Sizes (Same for All Models)
Terminal wire sizes are shown in Table 2.19.
Terminal
Pulse generator power supply
Pulse input terminal
Pulse monitor output terminal
Shield connection terminal
Straight Solderless Terminals for Control Circuit Terminals
We recommend using straight solderless terminal on signal lines to simplify wiring and improve reliability.
Refer to Table 2.10 Straight Solderless Terminal Sizes for specifications.
Closed-loop Connector Sizes and Tightening Torque
The closed-loop connectors and tightening torques for various wire sizes are shown in Table 2.20.
2
Wire Thickness [mm
]
0.5
0.75
1.25
2
Wiring Method and Precautions
The wiring method is the same as the one used for straight solderless terminals. Refer to page 2-24. Observe
the following precautions when wiring.
Separate the control signal lines for the PG Speed Control Board from main circuit lines and power lines.
Connect the shield when connecting to a PG. The shield must be connected to prevent operational errors
caused by noise. Also, do not use any lines that are more than 100 m long. Refer to Fig 2.23 for details on
connecting the shield.
Connect the shield to the shield terminal (E).
Do not solder the ends of wires. Doing so may cause contact faults.
When not using straight solderless terminals, strip the wires to a length of approximately 5.5 mm.
Table 2.19 Wire Sizes
Terminal
Wire Thickness (mm
Screws
Stranded wire: 0.5 to 1.25
-
Single wire: 0.5 to 1.25
M3.5
0.5 to 2
Table 2.20 Closed-loop Connectors and Tightening Torques
Terminal
Crimp Terminal Size
Screws
M3.5
Installing and Wiring Option Boards
2
)
• Shielded, twisted-pair wire
• Shielded, polyethylene-covered, vinyl
sheath cable
(KPEV-S by Hitachi Electric Wire or
equivalent)
Tightening Torque (N • m)
1.25 - 3.5
1.25 - 3.5
1.25 - 3.5
2 - 3.5
Wire Type
0.8
39
2-

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents