Time Chart
The following figure shows the frequency characteristics when L3-01 is set to 1.
Output current
Stall level during
acceleration
Output frequency
Fig 6.25 Time Chart for Stall Prevention During Acceleration
Setting Precautions
If the motor capacity is small compared to the Inverter capacity, or if the motor is operated using the fac-
tory settings, resulting in the motor stalling, lower the set value of L3-02.
If using the motor in the constant output range, L3-02 will be automatically lowered to prevent stalling.
L3-03 is the limit value to prevent the stall prevention level in the constant output range from being
reduced more than necessary.
Set the constants as a percent taking the Inverter rated voltage to be 100%.
Stall prevention level during
acceleration
Fig 6.26 Stall Prevention Level and Limit During Acceleration
Output frequency is controlled
to prevent the motor stalling.
E1-06
Base Frequency (FA)
Acceleration and Deceleration Characteristics
Time
Time
L3-02 (Stall Prevention Level during Accelera-
tion)
L3-02 x L3-03 (Stall Prevention Limit during Ac-
celeration)
Output frequency
31
6-